Plan Review Notes
Plan Review Notes For Permit 08070715
Permit Number 08070715
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-13 11:46:08 
 ** DENIED PLANS.**
  
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING MINIMUM CODES.
 FBC 2004 W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE INCLUDE MINIMUM LEVELS FOR ANY NEW
 HORN/STROBE DEVICES PER FBC 11-4.28.1,.2 AND .3 (4) FOR
 ADA.
  
 3) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR AUTOMATED LIGHTING CONTROLS REQUIRED. STATING ON
 PLANS MOTION SENSOR OR STANDARD SWITCH DOES NOT MEET
 THE MINIMUM PER CODE.
  
 4) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: PLANS SEEM TO BE SIGNED WITH SOME SORT OF
 INITIAL. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 DESIGN PROFESSIONAL PLEASE SUBMIT A SIGNED, DATED AND
 SEALED LETTER FOR SIGNATURE VERIFICATION. THIS LETTER
 NEEDS TO BE ORIGINAL AND NOTARIZED PER FS 117.05.
 FS 471.025
  
 6) NOTE: RISER SHOWS EQUIPMENT GROUNDING CONDUCTOR
 BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED.
 250.6,250.24. THIS CREATES OBJECTIONABLE CURRENTS.
  
 7) NOTE: PLEASE SEE NEW MECHANICAL COMMENTS AS THE
 COOLING LOAD CALCULATIONS WHICH ARE RAISED SEALS OVER A
 PHOTO-COPIED SIGNATURE WHICH IS IN VIOLATION OF FS
 471.025, FAC 61G15-23.002
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  