2008-08-13 11:46:08 | |
| ** DENIED PLANS.** |
| |
| |
| 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| THE FOLLOWING MINIMUM CODES. |
| FBC 2004 W/ 2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE INCLUDE MINIMUM LEVELS FOR ANY NEW |
| HORN/STROBE DEVICES PER FBC 11-4.28.1,.2 AND .3 (4) FOR |
| ADA. |
| |
| 3) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| FOR AUTOMATED LIGHTING CONTROLS REQUIRED. STATING ON |
| PLANS MOTION SENSOR OR STANDARD SWITCH DOES NOT MEET |
| THE MINIMUM PER CODE. |
| |
| 4) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| |
| 5) NOTE: PLANS SEEM TO BE SIGNED WITH SOME SORT OF |
| INITIAL. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| DESIGN PROFESSIONAL PLEASE SUBMIT A SIGNED, DATED AND |
| SEALED LETTER FOR SIGNATURE VERIFICATION. THIS LETTER |
| NEEDS TO BE ORIGINAL AND NOTARIZED PER FS 117.05. |
| FS 471.025 |
| |
| 6) NOTE: RISER SHOWS EQUIPMENT GROUNDING CONDUCTOR |
| BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT |
| PERMITTED. |
| 250.6,250.24. THIS CREATES OBJECTIONABLE CURRENTS. |
| |
| 7) NOTE: PLEASE SEE NEW MECHANICAL COMMENTS AS THE |
| COOLING LOAD CALCULATIONS WHICH ARE RAISED SEALS OVER A |
| PHOTO-COPIED SIGNATURE WHICH IS IN VIOLATION OF FS |
| 471.025, FAC 61G15-23.002 |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |