Plan Review Notes
Plan Review Notes For Permit 08070714
Permit Number 08070714
Review Stop P
Sequence Number 2
Notes
Date Text
2008-09-29 11:32:48PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. SHEET P1.1A PLAN KEYED NOTES DESCRIPTION #9 NEW EW:
 THE REFERENCE STANDARD FOR THE MIXING VALVE ANSI Z358.1
 DOES NOT COMPLY WITH THE FBC-2004 PLUMBING. PLEASE KNOW
 THAT TEMPERATURE-ACTUATED MIXING VALVES, WHICH ARE
 INSTALLED TO REDUCE WATER TEMPERATURE TO DEFINED
 LIMITS, SHALL COMPLY WITH ASSE 1017. PER FBC-2004
 PLUMBING SECTION 613.1 TEMPERATURE-ACTUATED MIXING
 VALVES.
  
 **RESPONSE NOTED, HOWEVER THE MIXING VALVE IN QUESTION
 IS FOR THE EYEWASH. THE REFERENCE STANDARD ANSI Z358.1
 FOR THE EYEWASH MIXING VALVE DOES NOT COMPLY WITH THE
 FBC-2004 PLUMBING. THE CORRECT STANDARD IS ASSE 1017.
 PER FBC-2004 PLUMBING SECTION 613.1,
 TEMPERATURE-ACTUATED MIXING VALVES.
  
 2. SHEET P1.1B WATER HEATER DETAIL #1:A MEANS OF
 CONTROLLING INCREASED PRESSURE CAUSED BY THERMAL
 EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2 .
  
 607.3.1 PRESSURE-REDUCING VALVE.
 FOR WATER SERVICE SYSTEM SIZES UP TO AND INCLUDING 2
 INCHES (51 MM), A DEVICE FOR CONTROLLING PRESSURE SHALL
 BE INSTALLED WHERE, BECAUSE OF THERMAL EXPANSION, THE
 PRESSURE ON THE DOWNSTREAM SIDE OF A PRESSURE-REDUCING
 VALVE EXCEEDS THE PRESSURE-REDUCING VALVE SETTING.
  
 607.3.2 BACKFLOW PREVENTION DEVICE OR CHECK VALVE.
 WHERE A BACKFLOW PREVENTION DEVICE, CHECK VALVE OR
 OTHER DEVICE IS INSTALLED ON A WATER SUPPLY SYSTEM
 UTILIZING STORAGE WATER HEATING EQUIPMENT SUCH THAT
 THERMAL EXPANSION CAUSES AN INCREASE IN PRESSURE, A
 DEVICE FOR CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 **RESPONE NOTED, HOWEVER THE RESUBMITTED DETAIL IS
 INDICATING THE EXPANSION TANK IN THE WRONG PLACE. THE
 EXPANSION TANK SHOULD BE LOCATED DOWNSTREAM OF THE
 WATTS 200 SERIES PRESSURE REGULATOR VALVE. THE
 RESUBMITTED DETAIL IS INDICATING THE EXPANSION TANK
 UPSTREAM OF THE PRESSURE REGULATOR VALVE. PLEASE
 CORRECT THIS PER FBC-2004 PLUMBING SECTION 607.3.1.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  