Plan Review Notes For Permit 08070714 |
Permit Number |
08070714 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-10-02 16:37:50 | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | REPEAT COMMENT: | | | | 2} INDICATE COMPLIANCE WITH THE POWER DENSITY | | REQUIREMENTS OF CHAPTER 13 FBC. THE INTERIOR LIGHTING | | POWER ALLOWANCE FOR A BUILDING OR A SEPARATELY METERED | | OR PERMITTED PORTION OF A BUILDING SHALL BE DETERMINED | | BY EITHER THE BUILDING AREA METHOD DESCRIBED IN SECTION | | 415.2.C.1 OR THE SPACE-BY-SPACE METHOD DESCRIBED IN | | SECTION 415.2.B.1. TRADE-OFFS OF INTERIOR LIGHTING | | POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING FOR | | WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN USED | | ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING | | POWER IDENTIFIED IN ACCORDANCE WITH SECTION | | 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING | | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION | | 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE | | PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN | | FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.*** | | NO CALCULATIONS GIVEN. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|