2008-09-24 16:02:09** DENIED 3RD REVIEW **
  
  
 ** 2ND REVIEW UNDER PERMIT APPLICATION.
  
  
 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS NOW
 SUBMITTED FOR FIRST REVIEW ARE NOT CORRECT AND DO NOT
 MEET FBC 13-415.2,13-415.2.ABC.1.1, .1.2.
 PLEASE SEE IN FACT THE LIGHTING WATTAGES AS SHOWN FOR
 MOST ALL OF THE FIXTURES IS INDICATING EACH FIXTURE AS
 35WATTS. HOW IS THIS POSSIBLE WHEN THE FIXTURE LEGEND
 CLEARLY INDICATES MANY OF THESE FIXTURES CONTAINING 3-
 T-8 BULBS? WHAT ARE THE WATTAGES OF THESE T-8 BULBS.
 BASED ON MOST MANUFACTURES ON THE MARKET, THIS OFFICE
 COULD NOT LOCATE ANY 11-13 WATT T-8 BULBS WHICH WOULD
 BE THE TOTAL AS SHOWN FOR EACH FIXTURE ON CALCULATIONS.
 PLEASE KNOW THAT EVEN WITH THE MOST EFFICIENT BALLAST
 ON THE MARKET KNOWN TO DATE, THE POWER FACTOR RATING
 WILL NOT TAKE 3-32WATT STANDARD T-* BULBS WHICH IS
 96WATTS AND TAKE THE RATING DOWN TO 35WATTS FOR ALL
 THREE BULBS IN A SINGLE FIXTURE. AS SHOWN ON PLANS THE
 AMOUNT OF LIGHT EXCEEDS THE ALLOWANCES IN THE FLORIDA
 BUILDING CODE.
 THE WATTAGE WHICH IS REQUIRED TO BE USED IS THE FIXTURE
 WATTAGE NOT THE BULB WATTAGE. BASED ON PLANS AND
 INFORMATION AT THIS TIME THIS DOES NOT MEET THE FBC
 SECTIONS AS NOTED.
 ** PLEASE BE SURE TO COMPLETE THE FIXTURES ON LEGEND.
 AN EXAMPLE WOULD BE THE RESTROOM LIGHT WHICH IS NOT
 SPECIFIED.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME. PLEASE KNOW ONE COPY OF
 ELECTRICAL PLANS/SHEETS HAVE BEEN RETAINED BY THIS
 OFFICE.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  