Plan Review Notes
Plan Review Notes For Permit 08070695
Permit Number 08070695
Review Stop P
Sequence Number 1
Notes
Date Text
2008-07-30 09:23:30PLUMBING PLAN REVIEW:
 DENIED:**FOR PLAN REVIEW ONLY NOT FOR PERMIT**
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-0 REQUIRED PLUMBING FIXTURES: THE
 REQUIREMENTS SHOULD BE BASED ON THE FBC- PLUMBING
 SECTION TABLE 403.1 FOR MERCANTILE NOT BUSSINESS.
 PLEASE CORRELATE THE REQUIRED PLUMBING FIXTURES WITH
 THE OCCUPANCY SUMMARY. PER FBC-2004 PLUMBING SECTION
 401.1 SCOPE AND TABLE 403.1 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES.
  
 2. SHEET P-1 SANITARY PLUMBING ISOMETRIC DETAIL #2:
 ONLY THE FIXTURES WITHIN THE BATHROOM GROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. (THE
 MOP SINK SHALL CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES). PER FBC- PLUMBING SECTION 909.1 WET VENT
 PERMITTED.
  
 3. SHEET P-1 GENERAL PLUMBING NOTES #15, STATES THE
 FOLLOWING "FURNISH AND INSTALL APPROVED AIR CHAMBERS AT
 EACH PLUMBING FIXTURE AND PDI APPROVED SHOCK ARRESTORS
 ON MAIN LINES AND RISERS". PLEASE KNOW THAT AIR
 CHAMBERS ARE NOT APPROVED BY FBC-2004 PLUMBING SECTION
 604.9 WATER HAMMER AND SHOULD BE DELETED FROM PLANS.
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 4. SHEET P-1 POTABLE WATER PLUMBING ISOMETRIC DETAIL
 #2: PLEASE PROVIDE THE FOLLOWING PER FBC-2004 PLUMBING
 SECTIONS.
  
 A} DELETE THE AIR CHAMBERS ON THE RISER DIAGRAM. PER
 SECTION 604.9 WATER HAMMER (REFERENCE COMMENT #3).
  
 B} PROVIDE THE REQUIRED THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER. PER SECTION 607.3 THERMAL EXPANSION
 CONTROL.
  
 5. SHEET P-1 WATER HEATER DETAIL #6: PLEASE PROVIDE
 THE FOLLOWING PER FBC-2004 PLUMBING SECTIONS.
  
 A} CLEARLY INDICATE THE HEIGHT OF THE WATER HEATER
 SHELF FROM FINNISH FLOOR TO THE TOP OF THE SHELF. PER
 SECTION 501.1 SCOPE.
  
 B} CLEARLY INDICATE THE REQUIRED TEMPERATURE AND
 PRESSURE RELIEF VALVE. PER SECTION 504.4 RELIEF VALVE.
  
 C} CLEARLY INDICATE THE T & P RELIEF VALVE IN THE TOP
 6 INCHES OF THE TANK BEING SERVED. PER SECTION 504.4.1
 INSTALLATION.
  
 D} CLEARLY INDICATE THAT THE T & P RELIEF VALVE SHALL
 DISCHARGE FULL SIZE TO A SAFE PLACE OF DISPOSAL SUCH AS
 THE FLOOR, WATER HEATER PAN, OUTSIDE THE BUILDING OR AN
 INDIRECT WASTE RECEPTOR. THE DISCHARGE PIPE SHALL NOT
 HAVE ANY TRAPPED SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING IN THE SAME ROOM AS THE WATER
 HEATER. PER SECTION 504.6.1 DISCHARGE.
  
 E} CLEARLY INDICATE THAT THE WATER HEATER PAN SHALL
 NOT BE LESS THAN 1-1/2 INCHES DEEP AND THE PAN DRAIN
 PIPE SIZE SHALL BE MINIMUM OF 3/4 INCHES IN DIAMETER.
 PER SECTION 504.7.1 PAN SIZE AND DRAIN.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]