2008-07-24 11:59:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 FOR PLAN REVIEW ONLY NOT FOR PERMIT.
 *** DENIED ***
  
 1) PLAN PAGE A-0 STATES "NO MECHANICAL WORK PROPOSED"
 BUT PLAN PAGE E-1 LIGHTING PLAN SHOWS 6 NEW 12X12
 RETURN AIR TRANSFER GRILLS WITH NO DUCTS. IS THE INTENT
 TO TURN THE ATTIC SPACE INTO A OPEN PLENUM? PLEASE
 SUBMIT MECHANICAL PLANS SHOWING ALL NEW AND ALTERED
 WORK, PER 2004 FBC 106.3.5.
  
 2) PLAN E-1 SHOW A NEW BATHROOM EXHAUST FAN BEING
 INSTALLED, PLEASE SHOW ON MECHANICAL PLAN AND SHOW WERE
 IT WILL DISCHARGE TO, PER 2004 FBC/M 401.5.2.
  
 3) PLAN E-1 ALSO SHOWS TWO NEW 24X48 RETURN AIR GRILLS
 AND ALL 24X24 SUPPLY AIR GRILLS BEING RELOCATED. PLEASE
 SHOW ON MECHANICAL PLAN WITH CFM'S AT ALL SUPPLY AIR
 GRILLS AND IF DUCT SIZES ARE BEING CHANGED SHOW NEW
 SIZE, PER 2004 FBC 106.3.5.
  
 4) PLEASE SHOW ON MECHANICAL PLAN OUTDOOR AIR
 CALCULATIONS, PER 2004 FBC/M 403.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]