Date |
Text |
2008-08-11 14:52:42 | |
| **DENIED** |
| |
| 1) NOTE: PLEASE KNOW PLANS ARE ONLY BEING SUBMITTED FOR |
| PLAN REVIEW AND ARE NOT BEING SUBMITTED UNDER PERMIT |
| APPLICATION. PLEASE KNOW EVEN ONCE PLANS ARE FOUND TO |
| BE CODE COMPLIANT PLANS WILL REMAIN IN A FAILED STATUS |
| UNTIL PERMIT IS APPLIED FOR. LICENSING OF DESIGNERS ETC |
| WILL BE VERIFIED AFTER PERMIT APPLICATION. |
| |
| ** PLEASE ALSO VERIFY THAT THE PLANS WERE ALREADY |
| SUBMITTED FOR *PLAN REVIEW * IN MARCH 08 UNDER TRACKING |
| NUMBER 08030346. |
| |
| 2) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| THE FOLLOWING MINIMUM CODES. |
| 2004 FBC W/2007 REVISIONS |
| 2003 NFPA-101 |
| 2002 NFPA-72 (WHERE APPLICABLE) |
| 2005 NFPA-70 |
| |
| ** STATING THE LATEST EDITION IS NOT PERMITTED. |
| |
| 2) NOTE: PLEASE KNOW BASED ON RISER AS SHOWN THE NEW |
| SERVICE IS NOT PERMITTED OR FALL UNDER THE EXCEPTIONS |
| OF 230.2 TO GRANT AN ADDITIONAL SERVICE. |
| |
| 3) NOTE: PLEASE SEE FBC 13-413.1.ABC.2.1 AND .2.2 AND |
| PROVIDE NOTES ON PLANS ACCORDINGLY. |
| |
| 4) NOTE: PLEASE PROVIDE LIGHTING CONTROLS ARE REQUIRED |
| PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE SEE 13-415.1.ABC.1.4 FOR ANY OUTSIDE LIGHTING. |
| SOME NOTES ON PLANS INDICATE SENSOR TYPE DEVICES OF |
| SOME KIND HOWEVER NOT ENOUGH INFORMATION IS PROVIDED. |
| NO TIMES ON DEVICES, DEVICES ARE NOT LISTED ON SYMBOL |
| LEGEND, NO OTHER INFORMATION PROVIDED. ETC. |
| |
| 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1 AND.1.2. |
| MUST ALSO SUBMIT A COMPLETED FIXTURE LEGEND WITH ALL |
| NEW FIXTURES. |
| |
| 6) NOTE: PLANS INDICATE CEILING MOUNTED OUTLET BOXES BY |
| LANDLORD HOWEVER AS THIS IS A SEPARATE LEGAL TENANT |
| SPACE COMMON AREAS SHALL NOT FEED INTO TENANT |
| SPACE(S). |
| PLEASE CONFIRM THAT THESE OUTLET BOXES ARE ACTUALLY |
| LOCATED ON THE OUTSIDE OF THIS TENANT SPACE. |
| |
| 7) NOTE: PLEASE INDICATE THE REQUIRED SHOW WINDOW |
| RECEPTACLES PER 210.62 AND LOADS PER 220.43A |
| |
| 8) NOTE: RISER SHOWS A 200AMP SERVICE HOWEVER |
| CONDUCTORS ON RISER ARE ONLY RATED FOR 150AMPS. 310.16 |
| |
| 9) NOTE: RISER INDICATES EQUIPMENT GROUNDING CONDUCTOR |
| BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT |
| PERMITTED 250.6,250.24 |
| |
| 10) NOTE: PLEASE EXPLAIN HOW WATER HEATER IS BEING |
| FIGURED INTO THE LOAD CALCULATIONS. PLEASE SEE 422.13 |
| AS WATER HEATER (STORAGE TYPE) ARE CONSIDERED A |
| CONTINUOUS LOAD AND NEEDS TO BE FIGURED AT 125%. |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |