Plan Review Notes
Plan Review Notes For Permit 08070695
Permit Number 08070695
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-11 14:52:42 
 **DENIED**
  
 1) NOTE: PLEASE KNOW PLANS ARE ONLY BEING SUBMITTED FOR
 PLAN REVIEW AND ARE NOT BEING SUBMITTED UNDER PERMIT
 APPLICATION. PLEASE KNOW EVEN ONCE PLANS ARE FOUND TO
 BE CODE COMPLIANT PLANS WILL REMAIN IN A FAILED STATUS
 UNTIL PERMIT IS APPLIED FOR. LICENSING OF DESIGNERS ETC
 WILL BE VERIFIED AFTER PERMIT APPLICATION.
  
 ** PLEASE ALSO VERIFY THAT THE PLANS WERE ALREADY
 SUBMITTED FOR *PLAN REVIEW * IN MARCH 08 UNDER TRACKING
 NUMBER 08030346.
  
 2) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING MINIMUM CODES.
 2004 FBC W/2007 REVISIONS
 2003 NFPA-101
 2002 NFPA-72 (WHERE APPLICABLE)
 2005 NFPA-70
  
 ** STATING THE LATEST EDITION IS NOT PERMITTED.
  
 2) NOTE: PLEASE KNOW BASED ON RISER AS SHOWN THE NEW
 SERVICE IS NOT PERMITTED OR FALL UNDER THE EXCEPTIONS
 OF 230.2 TO GRANT AN ADDITIONAL SERVICE.
  
 3) NOTE: PLEASE SEE FBC 13-413.1.ABC.2.1 AND .2.2 AND
 PROVIDE NOTES ON PLANS ACCORDINGLY.
  
 4) NOTE: PLEASE PROVIDE LIGHTING CONTROLS ARE REQUIRED
 PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415.1.ABC.1.4 FOR ANY OUTSIDE LIGHTING.
 SOME NOTES ON PLANS INDICATE SENSOR TYPE DEVICES OF
 SOME KIND HOWEVER NOT ENOUGH INFORMATION IS PROVIDED.
 NO TIMES ON DEVICES, DEVICES ARE NOT LISTED ON SYMBOL
 LEGEND, NO OTHER INFORMATION PROVIDED. ETC.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1 AND.1.2.
 MUST ALSO SUBMIT A COMPLETED FIXTURE LEGEND WITH ALL
 NEW FIXTURES.
  
 6) NOTE: PLANS INDICATE CEILING MOUNTED OUTLET BOXES BY
 LANDLORD HOWEVER AS THIS IS A SEPARATE LEGAL TENANT
 SPACE COMMON AREAS SHALL NOT FEED INTO TENANT
 SPACE(S).
 PLEASE CONFIRM THAT THESE OUTLET BOXES ARE ACTUALLY
 LOCATED ON THE OUTSIDE OF THIS TENANT SPACE.
  
 7) NOTE: PLEASE INDICATE THE REQUIRED SHOW WINDOW
 RECEPTACLES PER 210.62 AND LOADS PER 220.43A
  
 8) NOTE: RISER SHOWS A 200AMP SERVICE HOWEVER
 CONDUCTORS ON RISER ARE ONLY RATED FOR 150AMPS. 310.16
  
 9) NOTE: RISER INDICATES EQUIPMENT GROUNDING CONDUCTOR
 BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED 250.6,250.24
  
 10) NOTE: PLEASE EXPLAIN HOW WATER HEATER IS BEING
 FIGURED INTO THE LOAD CALCULATIONS. PLEASE SEE 422.13
 AS WATER HEATER (STORAGE TYPE) ARE CONSIDERED A
 CONTINUOUS LOAD AND NEEDS TO BE FIGURED AT 125%.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]