2008-07-23 16:39:422004 FBC W/2007 REVISIONS
 REROOF FLAT DECK
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS AS
 REQUIRED BY RULE 9B-72 AND FBC 106.1* CITY AMENDMENTS.
  
 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES,
 FASTENING OPTION AND DESIGN PRESSURE LISTED IN THE NOA
 WILL BE USED. FBC R301.1
  
 3) SUBMIT TWO COPIES OF SIGNED, SEALED AND DATED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AT PERIMETER
 AND CORNER AREAS FROM AN ENGINEER, ARCHITECT OR
 REGISTERED ROOF CONSULTANT AS REQUIRED BY LIMITATION
 NUMBER 7 ON PAGE 26 OF NOA NO. 07-0228.06. NOTE: THE
 ASSEMBLIES WITH LIMITATION #9 CAN NOT BE USED BECAUSE
 THE DESIGN PRESSURES ARE TOO LOW AND THEY CAN NOT BE
 INCREASED. THE STRUCTURE IS LOCATED IN EXPOSURE
 CATEGORY C.
  
 4) PROVIDE DOCUMENTATION THAT THE GENERAL CONTRACTOR'S
 LICENSE # CGCB03083 LISTED ON THE APPLICATION ALLOWS
 THE CONTRACTOR TO PERFORM REROOFING WORK WITHOUT A
 ROOFING CONTRACTING LICENSE AS REQUIRED BY FS 489.113.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]