2008-08-05 14:19:55*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3THE REMOVAL OF AND/OR STOCKING OF BUILDING MATERIALS
 AND SUPPLIES SHALL NOT BE STORED IN THE EXIT AISLE
 CORRIDORS AS TO HINDER OR INTERFERE WITH ACCESS TO /
 EGRESS FROM OTHER TENANT SPACES ON THE FLOOR OR THE
 BUILDING..
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.SPECIFY THE THE INTERIOR FINISH MATERIAL FOR ANY
 NEW WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 6.SHOW THE LOCATION OF THE SMOKE ALARMS (SA) FOR THE
 PROPOSED FLOOR PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  