Plan Review Notes For Permit 08070641 |
Permit Number |
08070641 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-08 10:23:23 | 2004 FBC W/2007 REVISIONS | | INSTALL 9 ACCORDION SHUTTERS | | | | DENIED BY BUILDING | | | | 1)SUBMIT TWO COPIES OF SHEETS 7 AND 8 OF THE PRODUCT | | APPROVAL DRAWINGS. THESE SHEETS CONTAIN THE ANCHOR | | SCHEDULE TABLES FOR THE 6.8 ACCORDION SHUTTERS. DCA | | RULE 9B-72 | | | | 2) THE BUILDING IS DIRECTLY ADJACENT TO MORE THAN 600 | | FEET OF OPEN AREAS OF EXPOSURE C-TYPE TERRAIN. | | THEREFORE, THE STRUCTURE IS CONSIDERED TO BE LOCATED IN | | EXPOSURE CATEGORY C. SEE FBC R 301.2.1.4 | | | | 3) IN ORDER TO USE THE ANCHOR SCHEDULE FOR CONCRETE,A | | MINIMUM OF 3350 PSI CONCRETE IS REQUIRED FOR THE ELCO | | TAPCONS AND 3000 PSI IS REQUIRED FOR ITW TAPCONS. IF | | USING THE ANCHOR SPACING FOR CONCRETE, SUBMIT PROOF | | THAT THE CONCRETE SUBSTRATE MEETS THE MINIMUM PSI | | REQUIREMENTS. OTHERWISE USE THE HOLLOW CONCRETE BLOCK | | ANCHOR SPACING SCHEDULE. SEE PRODUCT APPROVAL. | | | | 4) SPECIFY THE MINIMUM EDGE DISTANCE THAT WILL BE USED. | | SEE PRODUCT APPROVAL. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|