Plan Review Notes
Plan Review Notes For Permit 08070619
Permit Number 08070619
Review Stop G
Sequence Number 1
Notes
Date Text
2008-07-24 09:01:09GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. NOTE: THE SUBMITTED GAS PLANS CAN NOT BE APPROVED
 DUE TO THE FACT THAT THERE IS ALREADY AN APPROVED GAS
 PLAN FOR THE COMMERCIAL GENERATOR ON GEN/COM PERMIT
 #07040466 THAT IS SIGNED AND SEALED BY AN ARCHITECT.
 PLEASE KNOW THAT YOUR SUBMITTED PLANS ARE DIFFERENT
 THAN THE APPROVED PLANS BEING THAT THE APPROVED PLANS
 ARE INSTALLING 1-1/2" SCHEDULE 40 METALLIC ABOVE GROUND
 AND YOUR PLANS ARE USING 2" PE PIPING UNDERGROUND.
 IN ORDER TO RECIEVE A GAS PERMIT FOR THIS JOB THE
 RESUBMITTED PERMIT APPLICATION SHOULD STATE IN THE
 "DESCRIBE PROJECT IN DETAIL" SECTION OF THE PERMIT
 APPLICATION THE FOLLOWING, "GAS PERMIT PER APPROVED
 GEN/COM PERMIT #07040466." PLEASE KNOW THAT ANY CHANGES
 FROM THE APPROVED SET OF PLANS WILL HAVE TO HAVE THE
 ORIGINAL DESIGN PROFESSIONAL LEONARD LAFOREST RA
 #AROO14784 SUBMIT A SIGNED, SEALED, AND DATED REVISED
 GAS ISOMETRIC RISER DIAGRAM. PER CHAPTER 481, FLORIDA
 STATUTES, PART 1 AND FAC 61G1-16.004.
  
 END OF COMMENTS:
  