2008-07-22 16:08:21ROOFING, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 ***NOTE:BUILDING PERMIT REFERENCED ON PERMIT
 APPLICATION IS THREEYEARS OLD AND THERE IS NOT WORK
 AND INSPECTION ACTIVITY.
 EXPIRED PERMIT WASREVIEWED UNDER 2001 FBC.CURRENT
 BUILDING CODE IS 2004 FBC.PERMIT APPLICATION IS TO BE
 REVIEWED UNDER THE 2004 FBC.
  
 1- CLEARLY IDENTIFY SPECIFIC APPROVED ASSEMBLYAND
 SPECIFIC FASTENING OPTION TO BE INSTALLED AS REQUIRED
 BY CITY POLICY AND PROCEDURE FOR SUBMITTING PRODUCT
 APPROVALS FOR ROOFING/REROOFING PERMITS. SEE ATTACHED
 COPY.
  
 2- IF SELECTED ASSEMBLY AND FASTENING OPTION DOESN'T
 MEET THE DESIGN PRESSURES OF TABLE1609.6.2.1(2) OF
 FBC 2004 FOR FIELD, PERIMETER AND CORNER AREAS, THEN
 SIGNEDAND SEALEDRAS 117 CALCULATIONS WILL BE
 REQUIRED FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS.SEE GENERAL LIMITATION #7 ON SHEET 16 OF 16 OF
 NOA 06-0601.08 SUBMITTED.
  
 ***NOTE: NOTE: IF SELECTED ASSEMBLY IS LIMITED BY
 GENERAL LIMITATION #9 AND THE DESIGN PRESSURES DON'T
 MEET THE REQUIREMENTS OF THE ABOVE FBC 2004 TABLE, THEN
 THE ASSEMBLY CAN'T BE INSTALLED BECAUSE GENERAL
 LIMITATION #9 DOESN'T ALLOW NAILENHANCING.
  
 3- CLEARLY SPECIFYROOF SQUARE FOOTAGE TO PROPERLY
 ASSESS PERMIT VALUATION AS REQUIRED BY SEC. 108.3 OF
 CITY AMENDMENTS TO FBC 2004.
  