2008-07-22 08:43:09 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE LONGEST LENGTH OF 55' INDICATED ON THE PLANS IS |
| WRONG. THE CORRECT LONGEST LENGTH SHOULD BE 65'. PLEASE |
| CORRECT AND RESUBMIT. PER FBC-2004 FUEL GAS SECTION |
| 401.1 SCOPE AND THE CITY OF WEST PALM BEACH GAS PERMIT |
| APPLICATION REQUIREMENTS. |
| |
| 2. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: PLANS DO NOT INDICATE THE BTU LOAD TO EACH |
| APPLIANCE, HOWEVER THE PLANS ARE INDICATING A TOTAL BTU |
| LOAD OF 60,000. PLEASE CLEARLY INDICATE THE BTU LOAD TO |
| EACH APPLIANCE ON THE RESUBMITTAL. |
| |
| 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| (W.P.B. AS AMENDED) SECTION *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |