Notes |
Date |
Text |
2008-07-31 16:02:39 | ****************PROVISO**************** | | A} NOTE: THERE IS NO POOL TURNOVER TIME INDICATED IN | | THE SPECIFICATION. PER R4101.20 FILTERS. THE ENTIRE | | DESIGN OF MATCHED COMPONETS SHALL HAVE SUFFICIENT | | CAPACITY TO PROVIDE A COMPLETE TURNOVER OF POOL WATER | | IN 12 HOURS OR LESS. | | | | B} NOTE: THE POOL HEATER SHALL REQUIRE AN EXTERNAL | | HARTFORD LOOP. PER R4101.14.2 WATER RETENTION. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|