Plan Review Notes For Permit 08070576 |
Permit Number |
08070576 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-04 09:10:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.SEE OPENING 1.A 34IN OPENING WITH 3IN EDGE | | DISTANCE, SPAN SHOULD BE A MINIMUM OF 40IN, NOT 38IN. | | CHECK ALL; THIS COMMENT MAY APPLY TO OTHER OPENINGS. | | | | 2.SEE ACCORDION PRODUCT APPROVAL, PAGE 5 AND 10. WALL | | MOUNT 1 REQUIRES A CONCRETE SUBSTRATE, THIS JOB IS | | CONCRETE BLOCK.PLEASE REVISE AND CHECK ALL. | | | | 3.SEE ACCORDION PRODUCT APPROVAL, PAGE11.MINIMUM | | SPACING IS 3?; YOU HAVE SPECIFIED 2.49 FOR OPENINGS | | 3-6.ANCHORS CANNOT BE THIS CLOSE TOGETHER AS IT | | COMPROMISES THE SUBSTRATE (CAUSES IT TO SPLIT).PLEASE | | REVISE INSTALLATION SCHEDULE.CHECK ALL AND REVISE. | | | | 4.OPENING 3, CHECK SPAN.3 7/8" SHUTTER TO GLASS | | SEPARATION REQUIRED, NOT 3 5/16; SPAN SHOULD BE 106", | | NOT 104", PAGE 11 OF PRODUCT APPROVAL.CHECK ALL AND | | REVISE. | | | | |
|