Plan Review Notes
Plan Review Notes For Permit 08070576
Permit Number 08070576
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-04 09:10:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE OPENING 1.A 34IN OPENING WITH 3IN EDGE
 DISTANCE, SPAN SHOULD BE A MINIMUM OF 40IN, NOT 38IN.
 CHECK ALL; THIS COMMENT MAY APPLY TO OTHER OPENINGS.
  
 2.SEE ACCORDION PRODUCT APPROVAL, PAGE 5 AND 10. WALL
 MOUNT 1 REQUIRES A CONCRETE SUBSTRATE, THIS JOB IS
 CONCRETE BLOCK.PLEASE REVISE AND CHECK ALL.
  
 3.SEE ACCORDION PRODUCT APPROVAL, PAGE11.MINIMUM
 SPACING IS 3?; YOU HAVE SPECIFIED 2.49 FOR OPENINGS
 3-6.ANCHORS CANNOT BE THIS CLOSE TOGETHER AS IT
 COMPROMISES THE SUBSTRATE (CAUSES IT TO SPLIT).PLEASE
 REVISE INSTALLATION SCHEDULE.CHECK ALL AND REVISE.
  
 4.OPENING 3, CHECK SPAN.3 7/8" SHUTTER TO GLASS
 SEPARATION REQUIRED, NOT 3 5/16; SPAN SHOULD BE 106",
 NOT 104", PAGE 11 OF PRODUCT APPROVAL.CHECK ALL AND
 REVISE.
  
  