Plan Review Notes For Permit 08070532 |
Permit Number |
08070532 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-01 14:34:19 | ***DENIED*** | | | | 1) SHEET TWO ON LIFE SAFETY PLAN ILLUSTRATES AN | | EXISTING FIRE ALARM HORN. ARE THERE VISUAL APPLIANCES | | IN THIS AREA? | | | | 2) A DOOR LOCATED BETWEEN THE MUSIC ROOM AND AN | | EXISTING OFFICE SUITE IS NOT INDICATED AS AN EXIT DOOR, | | BUT SHOW AN EGRESS CAPACITY OF 135. EGRESS DOORS SHALL | | BE MARKED AND SHALL SWING IN THE DIRECTION OF TRAVEL | | WHERE SERVING (50) OR MORE OCCUPANTS. IF NOT AN EXIT | | DOOR, PLEASE REMOVE ANY REFERENCE TO EGRESS. | | ADDITIONALLY, PLEASE PROVIDE DOOR WIDTHS TO SUPPORT THE | | EGRESS CAPACITY CALCULATIONS ON THE DRAWINGS. | | | | 3) EGRESS DOOR SERVING A ROOM OR AREA WITH GREATER THAN | | (100) OCCUPANTS, SHALL BE PROVIDED WITH PANIC OR FIRE | | EXIT HARDWARE. PLEASE PROVIDE A DOOR SCHEDULE. | | | | 4) NOTE ON SHEET THREE INDICATES FIRE SPRINKLER TO | | REMAIN. IF SYSTEM IS TO BE ALTERED, SEPARATE SHOP | | DRAWINGS AND PERMIT REQUIRED. | | | | 5) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. | | | | 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|