2008-07-18 13:46:12 | RESIDENTIAL (R3)REROOF BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |
| 2-FLAT ROOF PRODUCT APPROVAL: |
| A) CLEARLY IDENTIFY/MARK APPROVED ASSEMBLY TO BE |
| INSTALLED AS REQUIRED BY THE CITY POLICY AND PROCEDURE |
| FOR ROOFING PERMITS. SEE ATTACHED COPY. |
| NEED TO IDENTIFY PAGE WITH SPECIFIC SELECTED ASSEMBLY |
| AND MARK SPECIFICBASE SHEET FASTENING OPTION. |
| |
| B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING |
| AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| LIMITATION #7. |
| |
| C) FASTENER SPACING FOR ANCHOR/BASE SHEET ATTACHMENT |
| SHOWN ON THE HIGH-VELOCITY HURRICANE ZONE PERMIT |
| APPLICATION FORM IS NOT CORRECT.SPACING OF NAILSIN |
| THE FIELD AREA SHALL BE THE AS NOTED IN THE PRODUCT |
| APPROVAL.PERIMETER AND CORNER AREAS NAIL SPACING |
| SHALL BE DONE ACCORDING TO THE RAS 117 CALCULATIONS AS |
| REQUIRED BY SEC. 8.1 OF RAS 117.REVISE AS REQUIRED. |
| |
| ***NOTE: PLEASE, DON'T SUBMIT PERMIT APPLICATION FROM |
| ANOTHER COUNTY. PROVIDE ONLY THE INFORMATION REQUIRED |
| IN THE CITY POLICY FOR ROOFING PERMITS. |
| |
| D) FLORIDA PRODUCT APPROVAL FL5680 DOESN'T |
| CORRESPOND TO NOA 03-0501.02.CORRECT FLORIDA PRODUCT |
| APPROVAL NUMBER IS FL617-R1. SEE ATTACHED COPY. REVISE |
| FOR FUTURE SUBMITTALS. |
| |
| 3- FLORIDA PRODUCT APPROVAL FL7849 SUBMITTED FOR |
| ROOFING TILES DOESN'T CORRESPOND TONOA 07-1023.12 |
| SUBMITTED. NOA 07-1023.12 MAY BE SUBMITTED ALONE |
| SINCE IT'S NOW LISTED IN THE CITY'S LIBRARY FILE FOR |
| LOCAL PRODUCT APPROVALS. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |
| |