2008-07-18 13:46:12RESIDENTIAL (R3)REROOF BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2-FLAT ROOF PRODUCT APPROVAL:
 A) CLEARLY IDENTIFY/MARK APPROVED ASSEMBLY TO BE
 INSTALLED AS REQUIRED BY THE CITY POLICY AND PROCEDURE
 FOR ROOFING PERMITS. SEE ATTACHED COPY.
 NEED TO IDENTIFY PAGE WITH SPECIFIC SELECTED ASSEMBLY
 AND MARK SPECIFICBASE SHEET FASTENING OPTION.
  
 B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 C) FASTENER SPACING FOR ANCHOR/BASE SHEET ATTACHMENT
 SHOWN ON THE HIGH-VELOCITY HURRICANE ZONE PERMIT
 APPLICATION FORM IS NOT CORRECT.SPACING OF NAILSIN
 THE FIELD AREA SHALL BE THE AS NOTED IN THE PRODUCT
 APPROVAL.PERIMETER AND CORNER AREAS NAIL SPACING
 SHALL BE DONE ACCORDING TO THE RAS 117 CALCULATIONS AS
 REQUIRED BY SEC. 8.1 OF RAS 117.REVISE AS REQUIRED.
  
 ***NOTE: PLEASE, DON'T SUBMIT PERMIT APPLICATION FROM
 ANOTHER COUNTY. PROVIDE ONLY THE INFORMATION REQUIRED
 IN THE CITY POLICY FOR ROOFING PERMITS.
  
 D) FLORIDA PRODUCT APPROVAL FL5680 DOESN'T
 CORRESPOND TO NOA 03-0501.02.CORRECT FLORIDA PRODUCT
 APPROVAL NUMBER IS FL617-R1. SEE ATTACHED COPY. REVISE
 FOR FUTURE SUBMITTALS.
  
 3- FLORIDA PRODUCT APPROVAL FL7849 SUBMITTED FOR
 ROOFING TILES DOESN'T CORRESPOND TONOA 07-1023.12
 SUBMITTED. NOA 07-1023.12 MAY BE SUBMITTED ALONE
 SINCE IT'S NOW LISTED IN THE CITY'S LIBRARY FILE FOR
 LOCAL PRODUCT APPROVALS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER