Plan Review Notes For Permit 08070523 |
Permit Number |
08070523 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-08-07 13:25:05 | RESIDENTIAL (R3) ROOFING, BUILDING REVIEW SECOND | | CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1-ENGINEERCALCULATIONS PROVIDED DON'T COMPLY WITH | | SECTION 9OF RAS 117 CALCULATIONS. CHECK THE NUMBER | | OF FASTENERS AND FASTENER SPACING REQUIREMENTS. PROVIDE | | ACTUAL CALCULATIONS ANDPROVIDE SKETCH SHOWING | | LOCATION OF FASTENERSAS REQUIRED BY FIGURE 3 OFRAS | | 117 CALCULATIONS. | | NOTE: MAKE SURETHE MINIMUM FASTENER SEPARATION MEETS | | THE REQUIREMENTS OF SEC. 8.1 OF RAS 117 CALCULATIONS. | | SEC. 106.1.2 CITY AMENDMENTS TOFBC 2004 TO VERIFY | | COMPLIANCE WITH RAS 117 CALCULATIONS. | | | | 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FL. ST.THIS MAY BE SUBMITTED AT TIME OF PERMIT PICK | | UP. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|