Plan Review Notes
Plan Review Notes For Permit 08070485
Permit Number 08070485
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-01 13:20:35***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. OK ON
 ELECTRICAL SHEETS. PLEASE ADD TO CODE ANALYSIS ON SHEET
 A-0.00.
  
 2) FIRE PROTECTION SYSTEMS ON SHEET A-0.00 INDICATES A
 FIRE ALARM. PLEASE INDICATE WHAT FIRE ALARM EQUIPMENT
 AND SHOW EQUIPMENT LAYOUT. SEPARATE SHOP DRAWINGS AND
 PERMIT REQUIRED FOR FIRE ALARM REMODEL IF APPLICABLE.
 IF NOT PART OF THIS PROJECT, PLEASE REMOVE REFERENCE
 FROM PLANS.
  
 3) IS PROJECT PROTECTED BY AUTOMATIC FIRE SPRINKLER
 SYSTEM? IF SO, PROVIDE SPRINKLER HEAD LAYOUT. SEPARATE
 SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE SPRINKLER
 REMODEL.
  
 4) PLANS INDICATE A TOTAL OF (3) EXITS. EACH EXIT
 APPEARS TO BE SEPARATED WITH NO COMMON PATH OF TRAVEL.
 PLEASE MAKE CORRECTION.
  
 5) PLANS SUGGEST EXISTING CONDITIONS THAT WILL REMAIN
 IN UNIT #105, BUT SCOPE OF WORK INCLUDES THIS UNIT. IF
 PART OF THE SCOPE OF THIS WORK, PLEASE CLARIFY AND SHOW
 NEW OR EXISTING EXIT SIGNS AND EMERGENCY LIGHTING
 FACILITIES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  