Plan Review Notes
Plan Review Notes For Permit 08070485
Permit Number 08070485
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-22 13:16:42 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE FIXTURE TYPES ON SHEET E-2 DO NOT MATCH THE THE
 TYPES ON SHEET A-2.01, THE NUBMER AND TYPES ON SHEET
 E-0 AND NONE OF THESE SHEETS MATCH THE THE NUMBER OR
 WATTAGE ON THE INPUT DATA REPORT. PLEASE CORRELATE ALL
 INFORMATION.
  
 2} THE AIR HANDLER AND COMPRESSER OCP IN THE PANEL
 SCHEDULES DO NOT CORRELATE WITH THE MANUFACTURERS
 SRECOMENDATION ON SHEET M-2. VERIFY THE OCP WITH THE
 MANUFACTURER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718