Plan Review Notes For Permit 08070485 |
Permit Number |
08070485 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-22 13:16:42 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE FIXTURE TYPES ON SHEET E-2 DO NOT MATCH THE THE | | TYPES ON SHEET A-2.01, THE NUBMER AND TYPES ON SHEET | | E-0 AND NONE OF THESE SHEETS MATCH THE THE NUMBER OR | | WATTAGE ON THE INPUT DATA REPORT. PLEASE CORRELATE ALL | | INFORMATION. | | | | 2} THE AIR HANDLER AND COMPRESSER OCP IN THE PANEL | | SCHEDULES DO NOT CORRELATE WITH THE MANUFACTURERS | | SRECOMENDATION ON SHEET M-2. VERIFY THE OCP WITH THE | | MANUFACTURER. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|