2008-08-04 11:29:51 | BUILDING PLAN REVIEW |
| PERMIT: 08070485 |
| ADD: 120 S. DIXIE HWY SUITE 103-105 |
| CONT: WILK CONSTRUCTION |
| TEL: (561)876-2724 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. |
| |
| 5)SHEET A-1.01 DOOR #101; FBC 11-4.13.6 MINIMUM |
| MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| OR POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE 25. THE |
| FLOOR OR GROUND AREA WITHIN THE REQUIRED CLEARANCES |
| SHALL BE LEVEL AND CLEAR. |
| |
| 6)THE LOUVERS IN THE EXTERIOR WALLS SHALL BE DESIGNED |
| TO RESIST WIND -DRIVEN RAIN WHERE THE RESULTS OF |
| TESTING INDICATE THAT WATER DID NOT PENETRATE CONTROL |
| JOINTS IN THE EXTERIOR WALL ENVELOPE, JOINTS AT THE |
| PERIMETER OF OPENINGS OR INTERSECTIONS OF TERMINATIONS |
| WITH DISSIMILAR MATERIALS. FBC 1403.2. LOUVERS |
| PROTECTING INTAKE AND EXHAUST VENTILATION DUCTS NOT |
| ASSUMED TO BE OPEN THAT ARE LOCATED WITHIN 30 FEET OF |
| GRADE SHALL MEET REQUIREMENTS OF LARGE MISSILE TEST. |
| 1609.1.4 (5). |
| |
| 7)PROVIDE THE PRODUCT APPROVALS FOR (A) LOUVERS (B) |
| LINTEL. THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL. 106.3* |
| |
| 8)SHEET A-1.01 AN UNOBSTRUCTED TURNING SPACE |
| COMPLYING WITH SECTION 11-4.2.3 SHALL BE PROVIDED |
| WITHIN AN ACCESSIBLE TOILET ROOM. THE CLEAR FLOOR SPACE |
| AT FIXTURES AND CONTROLS, THE ACCESSIBLE ROUTE, AND THE |
| TURNING SPACE MAY OVERLAP.THE CLEAR FLOOR SPACE SHALL |
| EXTEND A MAXIMUM OF 19 INCHES UNDERNEATH THE SINK (SEE |
| FIG 32). SEE ROOM #110 |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |