Plan Review Notes
Plan Review Notes For Permit 08070467
Permit Number 08070467
Review Stop E
Sequence Number 9
Notes
Date Text
2009-09-07 10:06:31 
 ** DENIED REVIEW OF REVISIONS**
  
 ** PLANS ARE FOR FINAL. NEED TO SHOW ALL ITEMS AS NOTES
 BELOW.
  
 1) NOTE: PLEASE SEE REDLINED PLANS NOTES FROM PREVIOUS
 REVIEW DATED 7/28/09 WITH RESPECT TO DISCONNECTS ON
 SHEETS NOT COORDINATING WITH RISER.
  
 2) NOTE: PLANS HAVE NOW BEEN REVISED FOR 3RD FLOOR
 REMOVING MOST LIGHTING EXCEPT FOR EGRESS PATH TO EXITS.
 HOWEVER NO LIGHTING CONTROLS FOR THESE LIGHTS ARE
 SHOWN?
 PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2 ( 2004 FBC. )
 PLEASE ALSO SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2.2 FOR
 ANY AUTOMATED CONTROLS SUCH AS OCCUPANCY SENSORS WHICH
 SHALL BE *FAIL SAFE ON* TYPE DEVICES.
  
 3) NOTE: THIS IS NOTED FOR INFORMATION ONLY. ASME-17
 FOR ELEVATOR LOBBY LIGHTING AT SILLS/LANDINGS. STATE
 ELEVATOR LIGHTING LEVELS.
 THIS IS NOTED ONLY.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  