2009-07-28 14:48:12 | ** REDLINED REVIEW ** | | | | 1) NOTE: THE REVISED ELEVATOR DISCONNECTS ON RISER ON | | M5 ARE NOT THE SAME AS ON M8. M5 SHOWS 200AMP WITH | | 125AMP FUSES, WHEREAS M8 SHOWS 100AMP DISCONNECTS WITH | | 100AMP FUSES. | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|