Plan Review Notes
Plan Review Notes For Permit 08070467
Permit Number 08070467
Review Stop E
Sequence Number 8
Notes
Date Text
2009-07-28 14:48:12** REDLINED REVIEW **
  
 1) NOTE: THE REVISED ELEVATOR DISCONNECTS ON RISER ON
 M5 ARE NOT THE SAME AS ON M8. M5 SHOWS 200AMP WITH
 125AMP FUSES, WHEREAS M8 SHOWS 100AMP DISCONNECTS WITH
 100AMP FUSES.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  