Plan Review Notes
Plan Review Notes For Permit 08070467
Permit Number 08070467
Review Stop E
Sequence Number 6
Notes
Date Text
2009-06-29 13:41:58** DENIED PLANS **
  
 ** SUBMITTED REVISIONS TO CHANGE SCOPE OF WORK TO ADD
 EXTERIOR LIGHTS.
  
  
 1) NOTE: PLANS NEED TO BE SUBMITTED REVISED BY THE
 ELECTRICAL DESIGNER OF RECORD.
 FS 471
  
 2) NOTE: WHEN SUBMITTING REVISED ELECTRICAL PLANS FOR
 ADDED SCOPE OF WORK FOR EXTERIOR LIGHTS. PLEASE SHOW
 COMPLIANCE FOR NEW OR EXISTING CONTROLS MEETING FBC
 13-415.1.ABC.1.4.
  
 3) NOTE: PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR
 LIGHTING.
  
 4) NOTE: PLEASE INCLUDE ANY NEW CIRCUITING. PLEASE KNOW
 THAT SPECS FOR INTERIOR OR EXTERIOR FIXTURES ARE NOT
 REQUIRED HOWEVER THE FIXTURE SCHEDULE ON PLANS NEEDS TO
 BE UPDATED TO INCLUDE ANY NEW FIXTURES, OR REVISED
 FIXTURES.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  