2008-10-24 07:46:20BUILDING PLAN REVIEW
 PERMIT: 08070467
 ADD: 303 BANYAN BLVD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4951
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
 OCT. 24, 2008
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) COMPLIED.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) COMPLIED.
 B) COMPLIED.
 C) COMPLIED.
 D) COMPLIED
 E) COMPLIED.
 F) COMPLIED
 G) COMPLIED
 H) COMPLIED
 I) COMPLIED.
  
 3)COMPLIED, VALUE OF $850,000.00.
  
 4-7) COMPLIED.
  
 8)SEMI-COMPLIED, THESE ARE NEW PRODUCT APPROVALS WITH
 NEW ISSUES. 609.1.4 PROTECTION OF OPENINGS IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE
 THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE3
 COPIES,OF PRODUCT APPROVALS YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING (3) PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 8A) STOREFRONT NOA 03-0801.04 MISSILE IMPACT RARING:
 NONE/ REQUIRES SHUTTERS
 8B) CURTAIN WALL SYSTEM SMALL MISSILE RATING IT APPEARS
 THIS SYSTEM WILL BE USED ONLY AT THE FRONT ENTRY
 REQUIRING LARGE MISSILE IMPACT
 8C) DOORS GLAZED- COMPLIED
 8D) DOORS LOUVERS NO SUBMITTALS
 8E) METAL INSULATED EXTERIOR DOORS- NO SUBMITTALS
 8F) LOUVERS- COMPLIED
 8G) STORM SHUTTERS/ USE OF WINDOWS WITH OUT LARGE
 MISSILE IMPACT
  
 8H) IN LEAU OF LARGE MISSLE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1606.1.4. FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 9-15) COMPLIED
  
 16) NEW COMMENT: REVISION TO PLANS SHEET A2.1 & A2.2
 BOTH INDICATE A CHANGE FROM STONE REVEAL AND MOLDINGS
 TO A FOAM TRIM PLEASE SEE 1406.2.2. USE OF FOAM
 MOLDINGS OR TRIM ABOVE 40 FEET.
 ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE SHALL BE CONSTRUCTED OF
 APPROVED NONCOMBUSTIBLE MATERIALS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.