2008-10-24 07:46:20 | BUILDING PLAN REVIEW |
| PERMIT: 08070467 |
| ADD: 303 BANYAN BLVD |
| CONT: LCI CONSTRUCTION |
| TEL: (561)307-4951 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3RD REVIEW |
| ACTION: DENIED |
| OCT. 24, 2008 |
| 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1E) COMPLIED. |
| |
| 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| OF OCCUPANCY: |
| A) COMPLIED. |
| B) COMPLIED. |
| C) COMPLIED. |
| D) COMPLIED |
| E) COMPLIED. |
| F) COMPLIED |
| G) COMPLIED |
| H) COMPLIED |
| I) COMPLIED. |
| |
| 3)COMPLIED, VALUE OF $850,000.00. |
| |
| 4-7) COMPLIED. |
| |
| 8)SEMI-COMPLIED, THESE ARE NEW PRODUCT APPROVALS WITH |
| NEW ISSUES. 609.1.4 PROTECTION OF OPENINGS IN |
| WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT |
| RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 |
| M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE |
| BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING |
| SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT |
| RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR |
| PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, |
| OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN |
| AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET |
| (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE |
| LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE |
| THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE |
| PROVISIONS OF THE SMALL MISSILE TEST. |
| |
| FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE3 |
| COPIES,OF PRODUCT APPROVALS YOUR PROJECT IS A THRESHOLD |
| BUILDING REQUIRING (3) PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS: |
| 8A) STOREFRONT NOA 03-0801.04 MISSILE IMPACT RARING: |
| NONE/ REQUIRES SHUTTERS |
| 8B) CURTAIN WALL SYSTEM SMALL MISSILE RATING IT APPEARS |
| THIS SYSTEM WILL BE USED ONLY AT THE FRONT ENTRY |
| REQUIRING LARGE MISSILE IMPACT |
| 8C) DOORS GLAZED- COMPLIED |
| 8D) DOORS LOUVERS NO SUBMITTALS |
| 8E) METAL INSULATED EXTERIOR DOORS- NO SUBMITTALS |
| 8F) LOUVERS- COMPLIED |
| 8G) STORM SHUTTERS/ USE OF WINDOWS WITH OUT LARGE |
| MISSILE IMPACT |
| |
| 8H) IN LEAU OF LARGE MISSLE IMPACT RATED WINDOWS, STORM |
| SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/ |
| 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT |
| PROTECTION |
| PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR |
| WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13 |
| RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES |
| WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE |
| SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT |
| MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE |
| THAT COMPLETE INSTALLATION OR SECURING IS DONE |
| SUFFICIENTLY IN ADVANCE OF THE HURRICANE? |
| |
| IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING, |
| CHAPTER 1, |
| ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE |
| BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| OF EXISTING BUILDINGS. |
| |
| IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| MULTI-STORY BUILDINGS, OR MULTIPLE |
| ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST |
| BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS |
| FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY |
| SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION |
| OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN |
| TWELVE (12) HOURS OR LESS OF THE |
| OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| OF A HURRICANE WATCH. |
| |
| PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| |
| PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| 1606.1.4. FL BLD CODE 2004 SECTION 106.3.3, |
| 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE |
| SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, |
| UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR |
| REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 9-15) COMPLIED |
| |
| 16) NEW COMMENT: REVISION TO PLANS SHEET A2.1 & A2.2 |
| BOTH INDICATE A CHANGE FROM STONE REVEAL AND MOLDINGS |
| TO A FOAM TRIM PLEASE SEE 1406.2.2. USE OF FOAM |
| MOLDINGS OR TRIM ABOVE 40 FEET. |
| ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN |
| HEIGHT ABOVE GRADE PLANE SHALL BE CONSTRUCTED OF |
| APPROVED NONCOMBUSTIBLE MATERIALS. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |