2008-09-10 16:06:12 | |
| |
| |
| |
| ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ALONG |
| WITH NEW NOTES DUE TO INFORMATION NOW SHOWN ON PLANS |
| WHICH WAS NOT ON PREVIOUS PLANS. |
| |
| 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE LEVELS FOR |
| EACH FLOOR NEEDS TO BE SHOWN. THE AMOUNT OF LIGHTING IN |
| DESIGN DOES NOT EXCEED ALLOWANCE PER 13-415.2.C TABLE |
| HOWEVER THE TOTAL DESIGN WATTAGE IS ABOUT HALF OF THE |
| ACTUAL WATTAGE FOR EACH FLOOR BASED ON THE FIXTURES ON |
| THE SCHEDULE. |
| 13-415.2.ABC.2.1, .2.2. |
| |
| 2) NOTE: PLEASE COMPLETE ALL FIXTURES ON PLANS. FOR |
| EXAMPLE THERE ARE A COUPLE OF FIXTURES WITH NOT |
| DESIGNATIONS AT ALL. *3RD FLOOR SOUTHEAST CORNER, AND |
| 4TH FLOOR CENTER. THESE COULD BE *ASSUMED* HOWEVER |
| PLANS NEED TO BE SPECIFIC. |
| ** THIS IS ONLY A NOTE, HOWEVER THERE IS ONLY *ONE* |
| TYPE *A* FIXTURE. ALL FIXTURES ON LIGHTING PLANS ARE |
| SHOWN AS *AE* WITH THE EXCEPTIONS AS NOTED. |
| PLEASE COORDINATE. |
| **** PLEASE COORDINATE THE FIXTURE DESIGNATIONS AND |
| OTHER INFORMATION FOR FIXTURES ON THE PHOTO-METRIC |
| PLANS WITH THE LIGHTING PLANS. THE NORMAL LIGHTING |
| LEVEL PHOTO-METRIC PLANS CALL FOR ALL TYPE *A* FIXTURES |
| YET THIS DOES NOT CORRESPOND TO LIGHTING PLANS. THIS |
| WAS NOTED PREVIOUSLY AND RESPONSE MENTIONS THIS WAS |
| CORRECTED HOWEVER BASED ON PLANS SUBMITTED THIS IS NOT |
| THE CASE. |
| 13-415.2.ABC.1.1, .1.2. |
| FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| |
| 3) NOTE: PLEASE SEE 230.2. AS STATED ON PREVIOUS REVIEW |
| AT THIS TIME THE NEW SERVICE AS SHOWN CAN NOT BE |
| PERMITTED. IN PHONE CONVERSATION WITH ENGINEER BEFORE |
| PLANS WERE RESUBMITTED, THIS REVIEWER ASKED TO PROVIDE |
| WHERE THIS WOULD MEET AN EXCEPTION TO ALLOW ANOTHER |
| SERVICE. THE RESPONSE LETTER MENTIONS BECAUSE OF THE |
| LOADS. HOWEVER BASED ON THE SECTION OF THE CODE AS |
| NOTED IF A SERVICE REACHES THE LIMIT OF 2000AMPS, THEN |
| AN ADDITIONAL SERVICE MAY BE GRANTED BY SPECIAL |
| PERMISSION. (SEE DEFINITIONS OF SPECIAL PERMISSION). |
| AT THIS TIME THE SERVICE IS NOT A SEPARATE VOLTAGE, IS |
| NOT OVER 2000 AMPS ETC. |
| |
| 4) NOTE: PLEASE VERIFY EQUIPMENT GROUNDING PATH FROM |
| MAINS TO SUB PANELS. |
| 250.110,250.122 |
| NEW NOTE: |
| |
| 5) NOTE: PLEASE CORRECT CODES ON ELECTRICAL NOTES. |
| PLEASE SEE NOTES MENTIONS THE STANDARD BUILDING CODE |
| AND MARTIN COUNTY AMENDMENTS. |
| THIS APPEARS TO BE A MISPRINT. |
| |
| SHOULD READ AS FOLLOWS. |
| 2004 FBC /W2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 AS ON OTHER SHEETS. |
| |
| 6) NOTE: VALUE FOR COMPLETE SCOPE OF WORK WAS INCREASED |
| BASED ON RESPONSE LETTER AND FEE BALANCE OF $7, 777.00 |
| WILL BE DUE BEFORE PERMIT CAN BE PRINTED. THE PERMIT |
| APPLICATION STATES TO DESCRIBE PROJECT IN DETAIL. THIS |
| WAS NOTED ON PREVIOUS REVIEW HOWEVER THE VALUE WAS |
| INCREASED BY THIS OFFICE AND APPLICATION NEEDS TO BE |
| DONE BY THE CONTRACTOR. |
| FBC 108.3 |
| |
| 7) NOTE: PLEASE SHOW CIRCUTING AND HOW LIGTHING WILL BE |
| CONTROLLED IN STAIRS. THE RESPONSE DOES NTO MENTION HOW |
| THIS WAS ADDRESSED AND PLANS DO NOT INDICATE ANY |
| CONTROLS. NFPA- 101 7.8.1.2.2, FBC 1006.1.2 |
| |
| 8) NOTE: PLEASE LIST MAXIMUM TIMES ON OCCUPANCY |
| SENSORS. IF THIS WAS THE ONLY COMMENT THIS WOULD HAVE |
| BEEN REDLINED. 13-415.1.ABC.1.1. |
| |
| |
| |
| |
| |
| ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH |
| INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK |
| WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE |
| REVIEW. |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |