Plan Review Notes
Plan Review Notes For Permit 08070467
Permit Number 08070467
Review Stop E
Sequence Number 2
Notes
Date Text
2008-09-10 16:06:12 
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ALONG
 WITH NEW NOTES DUE TO INFORMATION NOW SHOWN ON PLANS
 WHICH WAS NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE LEVELS FOR
 EACH FLOOR NEEDS TO BE SHOWN. THE AMOUNT OF LIGHTING IN
 DESIGN DOES NOT EXCEED ALLOWANCE PER 13-415.2.C TABLE
 HOWEVER THE TOTAL DESIGN WATTAGE IS ABOUT HALF OF THE
 ACTUAL WATTAGE FOR EACH FLOOR BASED ON THE FIXTURES ON
 THE SCHEDULE.
 13-415.2.ABC.2.1, .2.2.
  
 2) NOTE: PLEASE COMPLETE ALL FIXTURES ON PLANS. FOR
 EXAMPLE THERE ARE A COUPLE OF FIXTURES WITH NOT
 DESIGNATIONS AT ALL. *3RD FLOOR SOUTHEAST CORNER, AND
 4TH FLOOR CENTER. THESE COULD BE *ASSUMED* HOWEVER
 PLANS NEED TO BE SPECIFIC.
 ** THIS IS ONLY A NOTE, HOWEVER THERE IS ONLY *ONE*
 TYPE *A* FIXTURE. ALL FIXTURES ON LIGHTING PLANS ARE
 SHOWN AS *AE* WITH THE EXCEPTIONS AS NOTED.
 PLEASE COORDINATE.
 **** PLEASE COORDINATE THE FIXTURE DESIGNATIONS AND
 OTHER INFORMATION FOR FIXTURES ON THE PHOTO-METRIC
 PLANS WITH THE LIGHTING PLANS. THE NORMAL LIGHTING
 LEVEL PHOTO-METRIC PLANS CALL FOR ALL TYPE *A* FIXTURES
 YET THIS DOES NOT CORRESPOND TO LIGHTING PLANS. THIS
 WAS NOTED PREVIOUSLY AND RESPONSE MENTIONS THIS WAS
 CORRECTED HOWEVER BASED ON PLANS SUBMITTED THIS IS NOT
 THE CASE.
 13-415.2.ABC.1.1, .1.2.
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: PLEASE SEE 230.2. AS STATED ON PREVIOUS REVIEW
 AT THIS TIME THE NEW SERVICE AS SHOWN CAN NOT BE
 PERMITTED. IN PHONE CONVERSATION WITH ENGINEER BEFORE
 PLANS WERE RESUBMITTED, THIS REVIEWER ASKED TO PROVIDE
 WHERE THIS WOULD MEET AN EXCEPTION TO ALLOW ANOTHER
 SERVICE. THE RESPONSE LETTER MENTIONS BECAUSE OF THE
 LOADS. HOWEVER BASED ON THE SECTION OF THE CODE AS
 NOTED IF A SERVICE REACHES THE LIMIT OF 2000AMPS, THEN
 AN ADDITIONAL SERVICE MAY BE GRANTED BY SPECIAL
 PERMISSION. (SEE DEFINITIONS OF SPECIAL PERMISSION).
 AT THIS TIME THE SERVICE IS NOT A SEPARATE VOLTAGE, IS
 NOT OVER 2000 AMPS ETC.
  
 4) NOTE: PLEASE VERIFY EQUIPMENT GROUNDING PATH FROM
 MAINS TO SUB PANELS.
 250.110,250.122
 NEW NOTE:
  
 5) NOTE: PLEASE CORRECT CODES ON ELECTRICAL NOTES.
 PLEASE SEE NOTES MENTIONS THE STANDARD BUILDING CODE
 AND MARTIN COUNTY AMENDMENTS.
 THIS APPEARS TO BE A MISPRINT.
  
 SHOULD READ AS FOLLOWS.
 2004 FBC /W2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 AS ON OTHER SHEETS.
  
 6) NOTE: VALUE FOR COMPLETE SCOPE OF WORK WAS INCREASED
 BASED ON RESPONSE LETTER AND FEE BALANCE OF $7, 777.00
 WILL BE DUE BEFORE PERMIT CAN BE PRINTED. THE PERMIT
 APPLICATION STATES TO DESCRIBE PROJECT IN DETAIL. THIS
 WAS NOTED ON PREVIOUS REVIEW HOWEVER THE VALUE WAS
 INCREASED BY THIS OFFICE AND APPLICATION NEEDS TO BE
 DONE BY THE CONTRACTOR.
 FBC 108.3
  
 7) NOTE: PLEASE SHOW CIRCUTING AND HOW LIGTHING WILL BE
 CONTROLLED IN STAIRS. THE RESPONSE DOES NTO MENTION HOW
 THIS WAS ADDRESSED AND PLANS DO NOT INDICATE ANY
 CONTROLS. NFPA- 101 7.8.1.2.2, FBC 1006.1.2
  
 8) NOTE: PLEASE LIST MAXIMUM TIMES ON OCCUPANCY
 SENSORS. IF THIS WAS THE ONLY COMMENT THIS WOULD HAVE
 BEEN REDLINED. 13-415.1.ABC.1.1.
  
  
  
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH
 INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK
 WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE
 REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  