2008-09-22 15:33:47 | *****DENIED***** |
| |
| |
| 01. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 02. THE SCOPE OF WORK SHALL NOT HINDER OR OBSTRUCT |
| ACCESS TO / EGRESS FROM THE BUILDING AND/OR OTHER |
| BUILDINGS IN THE VICINITY INCLUDING STREETS, ROADS, |
| ALLEYS, FIRE LANES. |
| |
| 03. THE LOCATION OF THE NUMERICAL ADDRESS AS SHOWN ON |
| DRAWING A2.1 APPEARS TO BE TO HIGH TO BE READILY |
| VISIBLE FOR VISITORS AND/OR APPROACHING VEHICLES. |
| PLEASE BE ADVISED THAT ADDRESSES SHALL BE CLEARLY |
| VISIBLE FROM THE STREET. IN ADDITION, NUMBERS SHALL BE |
| NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| |
| 04. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| REFERENCED. |
| |
| 05. PLEASE EXPLAIN WHY THERE IS NO SPRINKLER LAYOUT FOR |
| THE 1ST FLOOR (FP-1) AND 2ND FLOOR (FP-2), BUT ARE |
| HOWEVER SHOWN ON THE 3RD FLOOR (FP-3) AND THE 4TH FLOOR |
| (FP-4)/ |
| |
| 06. SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR ANY |
| FIRE SPRINKLER INSTALLATION OR REMODEL. |
| |
| 07. SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C (IF |
| INCLUDED IN THIS SCOPE OF WORK). |
| |
| 08. SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS |
| I OR CLASS II (IF INCLUDED IN THIS SCOPE OF WORK). |
| |
| 09. SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR ANY |
| FIRE ALARM SYSTEM INSTALLATION OR REMODEL. |
| |
| 10. NFPA 72 - 2002 EDITION SHALL BE REFERENCED AS THE |
| FIRE ALARM STANDARD. |
| |
| 11. DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| ALARM AS PER LOCAL CODES. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| EACH ITEM WAS ADDRESSED |
| |
| |