Plan Review Notes
Plan Review Notes For Permit 08070467
Permit Number 08070467
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-09-22 15:33:47*****DENIED*****
  
  
 01. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02. THE SCOPE OF WORK SHALL NOT HINDER OR OBSTRUCT
 ACCESS TO / EGRESS FROM THE BUILDING AND/OR OTHER
 BUILDINGS IN THE VICINITY INCLUDING STREETS, ROADS,
 ALLEYS, FIRE LANES.
  
 03. THE LOCATION OF THE NUMERICAL ADDRESS AS SHOWN ON
 DRAWING A2.1 APPEARS TO BE TO HIGH TO BE READILY
 VISIBLE FOR VISITORS AND/OR APPROACHING VEHICLES.
 PLEASE BE ADVISED THAT ADDRESSES SHALL BE CLEARLY
 VISIBLE FROM THE STREET. IN ADDITION, NUMBERS SHALL BE
 NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 04. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 05. PLEASE EXPLAIN WHY THERE IS NO SPRINKLER LAYOUT FOR
 THE 1ST FLOOR (FP-1) AND 2ND FLOOR (FP-2), BUT ARE
 HOWEVER SHOWN ON THE 3RD FLOOR (FP-3) AND THE 4TH FLOOR
 (FP-4)/
  
 06. SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR ANY
 FIRE SPRINKLER INSTALLATION OR REMODEL.
  
 07. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C (IF
 INCLUDED IN THIS SCOPE OF WORK).
  
 08. SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS
 I OR CLASS II (IF INCLUDED IN THIS SCOPE OF WORK).
  
 09. SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR ANY
 FIRE ALARM SYSTEM INSTALLATION OR REMODEL.
  
 10. NFPA 72 - 2002 EDITION SHALL BE REFERENCED AS THE
 FIRE ALARM STANDARD.
  
 11. DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM AS PER LOCAL CODES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  