Plan Review Notes
Plan Review Notes For Permit 08070467
Permit Number 08070467
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-01 16:45:41 
 **DENIEDREVIEW**
  
 1) NOTE: PLEASE SEE THE LIFE SAFETY CODE NFPA-101 2003
 CHAPTER 7. PLEASE SEE SECTIONS 7.8 AND 7.9. PLEASE
 EXPLAIN HOW THE LIGHTING SHOWN FOR NORMAL USE IS
 DIFFERENT FIXTURES THAN THE LIGHTING SHOWN FOR
 EMERGENCY USE. THE FACT IS THESE ARE SHOWN AS
 COMPLETELY DIFFERENT FIXTURES.
 PLEASE SEE MISSING EXIT LIGHTS IN SEVERAL LOCATIONS.
 THIS MAY ALSO BE NOTED BY THE FIRE MARSHAL.
 PLEASE SEE 7.8.1.3, 7.9.2.1, 7.9.2.2 AND PLEASE SEE
 7.8.1.2.2 FOR FAIL SAFE CONTROLS. THIS IS ALSO IN FBC
 1006.1.2 (SEE COMMENTS BELOW FOR CHAPTER 13 LIGHTING
 CONTROLS REQUIRED).
 PLEASE SEE SECTIONS 7.10.1.1, 7.10.5.1 ETC. LOCATIONS
 WILL ALSO BE NOTED BY THE FIRE MARSHAL.
  
 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR MINIMUM CONTROLS REQUIRED FOR LIGHTING. PLEASE SEE
 NOTES ABOVE WITH RESPECT TO LIGHTING IN EGRESS AREAS.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 11. 11-4.28.1,.2,.3.
 PLEASE INDICATE THE MINIMUM LEVELS FOR ADA COMPLIANCE
 FOR ALL HORN/STROBE DEVICES.
  
 4) NOTE: PLEASE SEE 230.2AS THE NEW SERVICE WHICH IS
 NOW BEING SHOWN DOES NOT MEET THE EXCEPTIONS TO GRANT A
 NEW SERVICE.
 PLEASE SEE THE NEW MDP AS THIS SHOWS NEW 400AMP FEED TO
 NEW PANELS ON THIRD AND FORTH FLOORS YET BASED ON THE
 PANEL SCHEDULES THESE PANELS ARE SHOWN WITH A RATING OF
 400AMPS YET THEY ARE ALSO SHOWN WITH 150AMPMAIN LUG
 ONLY.
 WHAT IS THE VOLTAGE ON THE EXISTING SERVICE? SHOWN AS
 120/208 YET RISER ALSO SHOWS A TRANSFORMER.
  
 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1.ABC.1.1,..1.2.
  
 6) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.1.ABC.2.1,.2.2.
  
 7) NOTE: PLEASE INDICATE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 8) NOTE: PLEASE SEE THE APPLIED SCOPE OF WORK ON PERMIT
 APPLICATION STATES REPLACE WINDOWS AND STUCCO HOWEVER
 BASED ON PLANS THE SCOPE OF WORK IS SUBSTANTIALLY MORE.
 PLEASE KNOW THE PERMIT APPLICATION VALUE SHALL INCLUDE
 ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COSTS ETC PER
 FBC108.3 THIS IS FOR ALL TRADES.
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  