2008-08-01 16:45:41 | |
| **DENIEDREVIEW** |
| |
| 1) NOTE: PLEASE SEE THE LIFE SAFETY CODE NFPA-101 2003 |
| CHAPTER 7. PLEASE SEE SECTIONS 7.8 AND 7.9. PLEASE |
| EXPLAIN HOW THE LIGHTING SHOWN FOR NORMAL USE IS |
| DIFFERENT FIXTURES THAN THE LIGHTING SHOWN FOR |
| EMERGENCY USE. THE FACT IS THESE ARE SHOWN AS |
| COMPLETELY DIFFERENT FIXTURES. |
| PLEASE SEE MISSING EXIT LIGHTS IN SEVERAL LOCATIONS. |
| THIS MAY ALSO BE NOTED BY THE FIRE MARSHAL. |
| PLEASE SEE 7.8.1.3, 7.9.2.1, 7.9.2.2 AND PLEASE SEE |
| 7.8.1.2.2 FOR FAIL SAFE CONTROLS. THIS IS ALSO IN FBC |
| 1006.1.2 (SEE COMMENTS BELOW FOR CHAPTER 13 LIGHTING |
| CONTROLS REQUIRED). |
| PLEASE SEE SECTIONS 7.10.1.1, 7.10.5.1 ETC. LOCATIONS |
| WILL ALSO BE NOTED BY THE FIRE MARSHAL. |
| |
| 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| FOR MINIMUM CONTROLS REQUIRED FOR LIGHTING. PLEASE SEE |
| NOTES ABOVE WITH RESPECT TO LIGHTING IN EGRESS AREAS. |
| |
| 3) NOTE: PLEASE SEE FBC CHAPTER 11. 11-4.28.1,.2,.3. |
| PLEASE INDICATE THE MINIMUM LEVELS FOR ADA COMPLIANCE |
| FOR ALL HORN/STROBE DEVICES. |
| |
| 4) NOTE: PLEASE SEE 230.2AS THE NEW SERVICE WHICH IS |
| NOW BEING SHOWN DOES NOT MEET THE EXCEPTIONS TO GRANT A |
| NEW SERVICE. |
| PLEASE SEE THE NEW MDP AS THIS SHOWS NEW 400AMP FEED TO |
| NEW PANELS ON THIRD AND FORTH FLOORS YET BASED ON THE |
| PANEL SCHEDULES THESE PANELS ARE SHOWN WITH A RATING OF |
| 400AMPS YET THEY ARE ALSO SHOWN WITH 150AMPMAIN LUG |
| ONLY. |
| WHAT IS THE VOLTAGE ON THE EXISTING SERVICE? SHOWN AS |
| 120/208 YET RISER ALSO SHOWS A TRANSFORMER. |
| |
| 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP PER |
| 13-413.1.ABC.1.1,..1.2. |
| |
| 6) NOTE: PLEASE PROVIDE NOTES ON PLANS PER |
| 13-413.1.ABC.2.1,.2.2. |
| |
| 7) NOTE: PLEASE INDICATE LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| |
| 8) NOTE: PLEASE SEE THE APPLIED SCOPE OF WORK ON PERMIT |
| APPLICATION STATES REPLACE WINDOWS AND STUCCO HOWEVER |
| BASED ON PLANS THE SCOPE OF WORK IS SUBSTANTIALLY MORE. |
| PLEASE KNOW THE PERMIT APPLICATION VALUE SHALL INCLUDE |
| ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COSTS ETC PER |
| FBC108.3 THIS IS FOR ALL TRADES. |
| |
| ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE |
| NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |
| |
| |
| IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |