Plan Review Notes
Plan Review Notes For Permit 08070446
Permit Number 08070446
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-17 15:46:27RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- INSTALLATION SCHEDULE SUBMITTED CALLS FOROPENING
 #2 TO HAVECONNECTION TYPE"C1"ON TOP AND
 CONNECTION TYPE"C4"AT BOTTOM.ACCORDING TOPAGES
 4 AND 5 OFSHUTTERS DRAWING 05-AAS-0001 SUBMITTED
 CONNECTION TYPE"C4' IS NOT ALLOWED FOR CONNECTOR TYPE
 CIRCLED ON THE ANCHORSPACING TABLE. REVISE AS
 REQUIRED.
  
 2- ANCHOR TYPE SPECIFIED ON INSTALLATION SCHEDULE
 DOESN'T MATCHANCHOR TYPE CIRCLED ON THE ANCHOR
 SPACING TABLES ON SHEETS 4 AND 5OF DRAWING
 05-AAS-0001.REVISE AS REQUIRED TO MATCH.
  
 3-PANEL SPAN FOR OPENINGS #S 1,3, 4,7,9, 11 AND
 12 DON'T COMPLY WITHTABLE T3 OF SHEET 3 OF DRAWING
 05-AAS-0001 SUBMITTED.THE MINIMUM ALLOWABLE PANEL
 SIZEMUST BE MET TO COMPLY WITH THIS TABLE. REVISE AS
 REQUIRED.
  
 4- SHUTTER SPAN SIZE SHOWN ON INSTALLATION SCHEDULE
 SUBMITTED CAN'T NOT BE THE SAME SIZE AS THE OPENING.
 PANEL SPAN MUST BE LARGER IN ORDER TO PROVIDE THE
 MINIMUM EDGE DISTANCE.ALSO,STUCCO THICKNESS MUST BE
 CONSIDERED BECAUSE THE EDGE DISTANCE IS FOR THE ACTUAL
 FRAMING MEMBER EXCLUDING THE STUCCO THICKNESS. REVISE
 ASREQUIRED.
  
 5- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION
 WAS TOO LOW.PERMIT VALUATION WAS UPDATEDTO $2,553
 AS REQUIRED BY SEC. 108.3 OF CITY AMENDMENTS TO FBC
 2004.THEREFORE OWES #1.06 FOR UPDATED VALUATION.
  
 6- NEED TO PROVIDE RECORDED NOTICE OF COMMENCEMENT AS
 REQUIRED BY SEC. 713.13OF FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712