2008-07-17 15:46:27 | RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- INSTALLATION SCHEDULE SUBMITTED CALLS FOROPENING |
| #2 TO HAVECONNECTION TYPE"C1"ON TOP AND |
| CONNECTION TYPE"C4"AT BOTTOM.ACCORDING TOPAGES |
| 4 AND 5 OFSHUTTERS DRAWING 05-AAS-0001 SUBMITTED |
| CONNECTION TYPE"C4' IS NOT ALLOWED FOR CONNECTOR TYPE |
| CIRCLED ON THE ANCHORSPACING TABLE. REVISE AS |
| REQUIRED. |
| |
| 2- ANCHOR TYPE SPECIFIED ON INSTALLATION SCHEDULE |
| DOESN'T MATCHANCHOR TYPE CIRCLED ON THE ANCHOR |
| SPACING TABLES ON SHEETS 4 AND 5OF DRAWING |
| 05-AAS-0001.REVISE AS REQUIRED TO MATCH. |
| |
| 3-PANEL SPAN FOR OPENINGS #S 1,3, 4,7,9, 11 AND |
| 12 DON'T COMPLY WITHTABLE T3 OF SHEET 3 OF DRAWING |
| 05-AAS-0001 SUBMITTED.THE MINIMUM ALLOWABLE PANEL |
| SIZEMUST BE MET TO COMPLY WITH THIS TABLE. REVISE AS |
| REQUIRED. |
| |
| 4- SHUTTER SPAN SIZE SHOWN ON INSTALLATION SCHEDULE |
| SUBMITTED CAN'T NOT BE THE SAME SIZE AS THE OPENING. |
| PANEL SPAN MUST BE LARGER IN ORDER TO PROVIDE THE |
| MINIMUM EDGE DISTANCE.ALSO,STUCCO THICKNESS MUST BE |
| CONSIDERED BECAUSE THE EDGE DISTANCE IS FOR THE ACTUAL |
| FRAMING MEMBER EXCLUDING THE STUCCO THICKNESS. REVISE |
| ASREQUIRED. |
| |
| 5- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| WAS TOO LOW.PERMIT VALUATION WAS UPDATEDTO $2,553 |
| AS REQUIRED BY SEC. 108.3 OF CITY AMENDMENTS TO FBC |
| 2004.THEREFORE OWES #1.06 FOR UPDATED VALUATION. |
| |
| 6- NEED TO PROVIDE RECORDED NOTICE OF COMMENCEMENT AS |
| REQUIRED BY SEC. 713.13OF FLORIDA STATUTE. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |