2008-07-22 16:08:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.SEE OPENING 4, SPAN NOT CORRECT.A 77" OPENING,
 WALL MOUNT, WITH 3 1/2" EDGE DISTANCE SHOULD HAVE A
 SPAN OF 84".REVISE.CHECK ALL.
  
 2.CEILING MOUNT 5 IS HIGHLIGHTED, NOT SPECIFIED.IT
 IS NOT REQUIRED TO MARK THE PRODUCT APPROVAL BUT IF YOU
 DO, IT MUST CORRELATE WITH THE INSTALLATION SCHEDULE
 AND THIS JOB.
  
 3.SEE OPENING 1.FLOOR MOUNT 6 REQUIRES CONCRETE
 SUBSTRATE, SEE PRODUCT APPROVAL PAGE 11.
  
 4.#3 IS SPECIFIED FOR MOUNTING TYPE, #1 HIGHLIGHTED.
 #1 REQUIRES CONCRETE SUBSTRATE.CLARIFY.
  
 5.TWO COMPLETE SETS REQUIRED.ONLY ONE INSTALLATION
 SCHEDULE SUBMITTED.THE PERMIT CANNOT BE ISSUED
 WITHOUT TWO COMPLETE SETS.