2008-07-15 10:01:05 | 2004 FBC W/2007 REVISIONS |
| INSTALL 7 ACCORDION SHUTTERS AND 1 CLEAR PANEL SHUTTER |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SPECIFY WHICH ONE OF THE OPENINGS WILL RECEIVE THE |
| CLEAR STORM PANELS. |
| |
| 3) THE WRONG SECTION OF THE PRODUCT APPROVAL FOR THE |
| ACCORDION SHUTTERS WAS USED. THE MID-RISE PORTION, THAT |
| WAS USED, IS FOR SMALL MISSILE IMPACT PROTECTION ON |
| STRUCTURES ABOVE 30 FEET. SEE FBC 1609.1.4 THIS |
| STRUCTURE IS A SINGLE FAMILY RESIDENCE WITH A MEAN ROOF |
| HEIGHT OF LESS THAN 30 FEET, WHICH REQUIRES LARGE |
| MISSILE IMPACT PROTECTION. FBC R301.2.1.2. USE SHEETS 9 |
| THRU 16 OF THE PRODUCT APPROVAL. |
| |
| 4) THE RESIDENTIAL SECTION REQUIRES A MINIMUM 3-1/2 " |
| EDGE DISTANCE. ANYTHING LESS REQUIRES REDUCED ANCHOR |
| SPACING. SEE SHEET 14A OF PRODUCT APPROVAL. |
| |
| 5) THE SHUTTER SPANS ON THE INSTALLATION SCHEDULE ARE |
| INCORRECT. THE DIRECT MOUNT CLEAR PANEL SPAN WILL BE |
| THE OPENING PLUS THE TWO EDGE DISTANCES. THE ACCORDION |
| SHUTTER SPANS WILL BE A LITTLE MORE OR LESS THAN THE |
| OPENING HEIGHT DEPENDING ON HOW THEY ARE INSTALLED. THE |
| SCHEDULE INDICATES THAT ALL ARE INSTALLED VERTICALLY, |
| THEREFORE, THE SPAN WILL BE IN RELATION TO THE OPENING |
| HEIGHTS AND NOT THE WIDTHS AS INDICATE. PLEASE CORRECT. |
| SEE PRODUCT APPROVALS AS REQUIRED BY RULE 9B-72. |
| |