2008-07-11 14:17:18 | |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK |
| MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 |
| FAC. ONLY ONE SET IS SIGNED AND SEALED. |
| |
| 2} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| SHALL BE INTERCONNECTED AND HARD WIRED.***LOCATE ON THE |
| PLAN. |
| |
| 3} 9B-3.0472 CARBON MONOXIDE PROTECTION. |
| (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW |
| CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A |
| FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON |
| MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM |
| USED FOR SLEEPING PURPOSES. |
| (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR |
| PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING |
| IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS |
| SHALL HAVE BATTERY BACK UP. |
| (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING |
| LABORATORY. |
| SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED |
| 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. |
| HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLANIF |
| APPLICABLE.NOTE: MAY BE COMBINATION SMOKE/CARBON |
| MONOXIDE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |