Text |
2008-07-24 11:35:27 | RESIDENTIAL(R3)ADDITION, BUILDING REVIEW |
| CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1-A) PROPERTY IS LOCATED ON FLOOD ZONE A5WITH BASE |
| FLOOD ELEVATION OF 7'. IF EXISTING HOUSE AND |
| PROPOSED ADDITION FINISH FLOOR ELEVATION IS LESS THAN |
| 7'-6", THEN THE HOUSE NEEDS TO BE RAISED AS REQUIRED BY |
| CITY ORDINANCESEC. 94-546(A) AND (B).PROVIDE |
| SURVEY OR ANY OTHERDOCUMENT SHOWING EXISTING FINISH |
| FLOOR ELEVATION TO VERIFY COMPLIANCE WITH THIS CODE |
| ORDINANCE. |
| |
| B) PROPOSED PLANS NEED TO SHOW THE PROPOSED FINISH |
| FLOOR ELEVATION TO SHOW COMPLIANCE WITH THIS CITY |
| ORDINANCE. |
| |
| 2- SHEET #1: |
| A) SPECIFYATTIC LIVE LOAD AS REQUIRED BY TABLE |
| R301.5 OF 2004 FLORIDA RESIDENTIAL CODE. |
| ***NOTE: COORDINATELOADS WITH TRUSS ENGINEER. SEE |
| TRUSS PACKAGE.EG: PROJECT NOTES CALL FOR 30PSF ROOF |
| LIVE LOAD. COORDINATE AND REVISE AS REQUIRED. |
| |
| B) ENTRY PORCH FOUNDATION PLAN: SPECIFY HOW MUCH |
| EMBEDMENT IS REQUIRED FOR ANCHOR BOLTSAT BASE OF |
| STEEL COLUMN. SEC.106.1.2 CITY AMENDMENTS TO FBC 2004 |
| TO VERIFY COMPLIANCE WITH UPLIFT LOADS SEC. R301 2004 |
| FLORIDA RESIDENTIAL CODE. |
| |
| C) REVISE LEVEL ALTERATION TYPE SHOWN ON PROJECT |
| NOTES. SEECHAPTER 3 OF THE EXISTING BUILDING CODE |
| 2004TO VIEW SCOPE OF WORK AND REVISE AS REQUIRED. |
| |
| 3- SHEET #2: |
| A) PROVIDE ATTIC ACCESSFOR NEW ADDITION AS |
| REQUIRED BY SEC. R807 OF 2004 FLORIDA RESIDENTIAL |
| CODE. |
| |
| B) SPECIFY SIZE OF NEW ATTIC ACCESSWITH DROP |
| LADDER TO VERIFY COMPLIANCE WITH SEC. R807. |
| |
| 4- SHEET#3, TYPICAL WALL SECTION: |
| A)REVISE ROOF SHEATHING FASTENING OPTION FOR ROOF |
| ZONE #3 AS REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| B) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2 |
| OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| C) CLEARLY SPECIFY ROOF TILE FASTENING AS REQUIRED |
| BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. ***NOTE: |
| COORDINATE WITH PRODUCT APPROVAL SUBMITTED. SEE SHEET |
| 12 OF NOA 07-1129.04 SUBMITTED AND REVISE INFORMATION |
| ON WALL SECTION AS REQUIRED. |
| |
| D) INDICATE LINE OF GRADE TO VERIFY COMPLIANCE WITH |
| FOOTING MINIMUM DEPTH SEC. R403.1.4 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| 5- SHEET #4: SPECIFY SIZE OF STEEL CORNER BUCKET FOR |
| STEEL COLUMNS. |
| |
| 6- OWES #5.90 FOR RADON FEES. |
| |
| 7- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| *** NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK |
| UP. |
| |
| 8- PROVIDE ENERGY CALCULATIONS AS REQUIRED BYSEC. |
| 13-101.2 FBC 2004. |
| NOTE: MAKE SURE CORRECT REVISED FORM IS USED TO AVOID |
| DELAYS OR CONFLICTS. |
| |
| 9- SOIL TEST REPORT SUBMITTED: |
| A) NEEDS TO HAVE ENGINEER'S ORIGINAL SIGNATURE (NO |
| COPY) AS REQUIRED BY SEC. 61G15-23.002 (1) OF FLORIDA |
| ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. |
| |
| B) NEEDS TO HAVE THE ENGINEERING FIRM CERTIFICATE OF |
| AUTHORIZATION NUMBER AS REQUIRED BY SEC. |
| 61G15-23.002(2). FLORIDA ADMINISTRATIVE CODE. |
| |
| 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) WINDOW MULLIONS.AND CLEARLY MARKSPECIFIC |
| MULLION SIZE AND FASTENERS TO BE USED TO VERIFY |
| COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES OF SEC. |
| R301. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS AND DETAILS. |
| NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE AND PAGE WHERE CONNECTOR IS LOCATED. NO NEED TO |
| SUBMIT COMPLETE PRODUCT APPROVAL REPORT. |
| |
| 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCTAPPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| NOTE: SEPARATE LETTER SUBMITTED BY THE ENGINEER IS |
| INCOMPLETE. IT'SNO LISTING ALL PRODUCT APPROVALS AND |
| IS NOT LISTING THE SPECIFIC FLORIDAPRODUCT APPROVAL |
| OR NOANUMBER REVIEWED. |
| |
| 12- TRUSS PACKAGE: |
| A) INDEX SHEET DOESN'TCOMPLY WITH THE REQUIREMENTS |
| OF SEC. 61G15-31.003.THE NAME OF THE ENGINEER OF |
| RECORD IS NOT SHOWN AND ALL INDIVIDUAL TRUSSES NEED TO |
| HAVE THE TRUSS ENGINEER NAME AND INFORMATION. REVISE AS |
| REQUIRED. |
| |
| B) TRUSS PACKAGE NEEDS TO BE REVIEWED BY THE |
| ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. |
| |
| C) PROVIDE ONLY 2 COMPLETE COPIES WITH ORIGINAL SEAL |
| AND SIGNATURE.(FOUR COPIES WHERE SUBMITTED AND TWO OF |
| THOSE HAD NO ORIGINAL SIGNATURE). |
| |
| |
| ***NOTE: PLEASE RESUBMIT PAGES WITH PALM BEACH COUNTY |
| IMPACT FEES STAMP. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |