Plan Review Notes
Plan Review Notes For Permit 08070268
Permit Number 08070268
Review Stop M
Sequence Number 2
Notes
Date Text
2008-09-18 11:23:35REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 3: OK
  
 4. PLEASE SEE PREVIOUS MECHANICAL REVIEW COMMENT #4 AND
 CURRENT BUILDING COMMENT #14 REGARDING THE INCOMPLETE
 ROOF CURB DETAIL ON PAGE S-3. PROVIDE ALL INFORMATION
 FOR ATTACHMENT OF ROOF CURB TO STRUCTURE TO DEOMNSTRATE
 COMPLIANCE WITH THE REQUIREMENTS OF FBCM 301.13 FOR
 WIND RESISTANCE. ALSO, NO INFORMATION WAS PROVIDED
 REGARDING WIND RESISTANCE OF THE ROOF VENTILATOR HOOD
 SHOWN IN DETAIL #3 ON PAGE M-8. PROVIDE DOCUMENTATION
 FROM THE MANUFACTURER OF THIS HOOD WHICH DEMONSTRATES
 COMPLIANCE WITH THIS SECTION.
  
 5. OK
  
 6. MECHANICAL PORTIONS OF THE ENERGY CODE COMPLIANCE
 FORM AND COOLING LOAD CALCULATIONS ARE OK. HOWEVER, THE
 ENERGY CODE COMPLIANCE FORM WILL REMAIN IN FAIL STATUS
 PENDING SUCCESSFUL REVIEW BY ALL INTERESTED TRADES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: