Plan Review Notes For Permit 08070268 |
Permit Number |
08070268 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-09-18 11:23:35 | REVIEW #: 2ND | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | 1 THROUGH 3: OK | | | | 4. PLEASE SEE PREVIOUS MECHANICAL REVIEW COMMENT #4 AND | | CURRENT BUILDING COMMENT #14 REGARDING THE INCOMPLETE | | ROOF CURB DETAIL ON PAGE S-3. PROVIDE ALL INFORMATION | | FOR ATTACHMENT OF ROOF CURB TO STRUCTURE TO DEOMNSTRATE | | COMPLIANCE WITH THE REQUIREMENTS OF FBCM 301.13 FOR | | WIND RESISTANCE. ALSO, NO INFORMATION WAS PROVIDED | | REGARDING WIND RESISTANCE OF THE ROOF VENTILATOR HOOD | | SHOWN IN DETAIL #3 ON PAGE M-8. PROVIDE DOCUMENTATION | | FROM THE MANUFACTURER OF THIS HOOD WHICH DEMONSTRATES | | COMPLIANCE WITH THIS SECTION. | | | | 5. OK | | | | 6. MECHANICAL PORTIONS OF THE ENERGY CODE COMPLIANCE | | FORM AND COOLING LOAD CALCULATIONS ARE OK. HOWEVER, THE | | ENERGY CODE COMPLIANCE FORM WILL REMAIN IN FAIL STATUS | | PENDING SUCCESSFUL REVIEW BY ALL INTERESTED TRADES. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|