Plan Review Notes
Plan Review Notes For Permit 08070268
Permit Number 08070268
Review Stop M
Sequence Number 1
Notes
Date Text
2008-07-22 16:21:07REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M-4: ELECTRICAL ROOM 123 IS SHOWN ON PAGES LS-1 AND
 A-1 TO BE 1-HOUR FIRE RESISTANCE RATED. MECHANICAL
 FLOOR PLAN SHOWS TWO UNPROTECTED DUCT PENETRATIONS INTO
 THIS ROOM. PLEASE COORDINATE THE LOCATIONS OF RATED
 WALL ASSEMBLIES WITH LS AND A PAGES, SHOWING DUCT
 PENETRATIONS TO BE PROTECTED IN ACCORDANCE WITH FBCM
 607.5.
  
 2. M-4: LAUNDRY ROOM 135 SHOWS 2 CLOTHES DRYERS. NOTE
 #6 CALLS FOR TWO 6? ROUND DUCTS. IT IS NOT KNOWN
 WHETHER THESE ARE DOMESTIC OR COMMERCIAL DRYERS. PLEASE
 PROVIDE SUBMITTAL WITH MANUFACTURER?S INSTALLATION
 INSTRUCTIONS TO SHOW COMPLIANCE WITH THE FOLLOWING
 REQUIREMENTS:
  
 A) CLOTHES DRYERS SHALL BE EXHAUSTED IN ACCORDANCE WITH
 THE MANUFACTURER?S INSTRUCTIONS PER FBCM 504.1.
 DOMESTIC DRYERS GENERALLY REQUIRE 4? ROUND DUCTS.
 LARGER DUCTS REDUCE AIR VELOCITY AND CONTRIBUTE TO THE
 BUILD-UP OF LINT WITHIN THE EXHAUST DUCTS.
  
 B) INSTALLATIONS EXHAUSTING MORE THAN 200 CFM SHALL BE
 PROVIDED WITH MAKEUP AIR IN ACCORDANCE WITH FBCM 504.5.
 IT IS NOT KNOWN THE RATE OF EXHAUST FOR THE TWO DRYERS
 COMBINED. THERE IS NO MAKEUP AIR SHOWN ON FLOOR PLANS
 AS THERE IS EQUALIZED SUPPLY AND EXHAUST IN THE ROOM.
  
 3. M-4: SOME DUCT SIZES ARE MISSING ON FLOOR PLANS.
 EXAMPLES: RETURN DUCT FOR TELE CLOSET 137, ROUND TRUNK
 LINE UPSTREAM OF TB 1-4, EXHAUST RISER FOR EF 1-1.
 PLEASE CHECK ALL DUCTS FOR SIZING AND PROVIDE MISSING
 INFORMATION ON PLANS. AN AIR DISTRIBUTION SYSTEM SHALL
 BE DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
  
 4. M-8: DETAILS 2 AND 3REFERENCE STRUCTURAL PLANS FOR
 CURB ATTACHMENT DETAIL. NO SUCH DETAIL COULD BE LOCATED
 IN STRUCTURAL PLANS. PROVIDE DETAIL SHOWING CURBS, FANS
 AND VENTS DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 5. EXHAUST FANS AND DRYER VENT OUTLET ARE LOCATED ON A
 ROOF EXCEEDING 16? IN HEIGHT. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET, SUCH
 ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS
 OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR
 FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL
 SERVICE SPACE IN ACCORDANCE WITH FBCM 306.5. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES IN HEIGHT. PAGE A-2 ON THE
 EXISTING PORTION MAKES REFERENCE TO SOME TYPE OF LADDER
 ON ROOF BUT NO ADDITIONAL INFORMATION COULD BE FOUND.
 PLEASE PROVIDE SUFFICIENT DETAIL TO DEMONSTRATE
 COMPLIANCE WITH THIS SECTION.
  
 6. ENERGY CALCULATIONS: A FULL REVIEW OF THE ENERGY
 CODE COMPLIANCE FORMS CAN NOT BE DONE AT THIS TIME
 BECAUSE THE INPUT DATA REPORT WAS NOT INCLUDED IN THE
 SUBMISSION. SEE ?IMPORTANT NOTE? ON PAGE 2. ALSO SEE
 THE INPUT REPORT IS CALLED FOR (AND CHECKED) ON THE
 CHECKLIST ON PAGE 7.
  
 EVEN THOUGH THE ENERGY CALCULATIONS ARE NOT BEING
 REVIEWED, THE FOLLOWING CORRECTIONS SHOULD BE MADE
 PRIOR TO RESUBMISSION:
  
 A) ENERGY CODE CALCULATIONS SHALL BE MADE A PART OF THE
 PLANS AND SPECIFICATIONS OF THE BUILDING AND THE PLANS
 AND SPECIFICATIONS SHALL BE PREPARED BY AN ENGINEER OR
 ARCHITECT LICENSED TO PRACTICE IN THE STATE OF FLORIDA
 IN ACCORDANCE WITH FBCB 13-103.2. THE CERTIFICATIONS
 PAGE STATES THE CALCULATIONS WERE PREPARED BY ?JARMO J.
 VALIMAKI.? IS THIS PERSON A FLORIDA LICENSED ENGINEER
 OR ARCHITECT? ALSO, THE PERSON PREPARING THE COMPLIANCE
 CALCULATION SHALL CERTIFY (BY SIGNING AND SEALING) THAT
 THE PLANS AND SPECIFICATIONS COVERED BY THE CALCULATION
 ARE IN COMPLIANCE WITH CHAPTER 13 OF THE FLORIDA
 BUILDING CODE IN ACCORDANCE WITH FBCB 13-103.1.1.
  
 B) A SYSTEM SIZING SUMMARY HAS BEEN ATTACHED TO THE
 ENERGY CALCULATIONS. THE SUMMARY SHALL BE SIGNED AND
 SEALED BY THE MECHANICAL ENGINEER IN ACCORDANCE WITH
 FBCB 13-407.1.ABC.1 EXCEPTION 1.
  
 C) THE SUMMARY CALLS FOR A REQUIRED TOTAL COOLING
 CAPACITY OF 132,072 BTU/H. THE NEW CHILLER IS SHOWN ON
 SCHEDULE AS 24 TONS, WHICH IS MORE THAN DOUBLE THE
 REQUIRED COOLING CAPACITY SHOWN ON THE SUMMARY. HVAC
 SYSTEMS AND EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE
 THAN THE SPACE AND SYSTEM LOADS CALCULATED IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 NOTE: ALSO, CHECK THE HOT WATER PIPING INSULATION
 THICKNESS IN THE CALCULATIONS AGAINST THE THICKNESSES
 WHICH ARE CALLED FOR IN THE JOB SPECIFICATIONS.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH AN
 EXPLANATION OF HOW THE COMMENTS WERE ADDRESSED AS WELL
 AS WHERE THE RELATED INFORMATION CAN BE LOCATED. THIS
 WILL HELP TO FACILITATE TIMELY SUBSEQUENT REVIEWS. ALSO
 PLEASE PROVIDE ONE SET OF OLD, VOIDED PLANS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]