Plan Review Notes For Permit 08070262 |
Permit Number |
08070262 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-11 09:32:44 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLEASE SHOW THE SIZE OF THE SUPPLY AIR TRUNK LINE ON | | PLAN, PER 2004 FBC 106.3.5. | | | | 2) SHOW ON PLANS HOW THE AIR IS RETURNING TO THE AIR | | HANDLER UNIT, IF GRILL SHOW GRILL SIZES, PER 2004 FBC/M | | 601.4. | | | | 3) SHOW ON PLANS THE OUTDOOR AIR CALCULATIONS AND HOW | | MUCH OUTDOOR AIR IS TO BE PROVIDED, PER 2004 FBC/M | | 403.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|