2008-07-08 10:32:46 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS |
| AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THERE ARE NINE BAYS WITH PANELS SHOWN ON THE FLOOR |
| PLAN, ONLY EIGHT PANELS SHOWN ON THE RISER DIAGRAM. SEE |
| 240.24(B). PLEASE CORRELATE SAME. |
| |
| 2} 230.2 NUMBER OF SERVICES |
| A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) |
| THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 |
| ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND |
| LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED |
| TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER |
| AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING |
| ONE SERVICE. THERE ARE TWO OVERHEAD SERVICES SHOWN |
| WHICH IS IN VIOLATION OF THIS ARTICLE.SEE 230.40 |
| EXCEPTION #2 AND INDICATE IF THAT EXCEPTION APPLIES. |
| |
| 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| DESIGNED.NOTE #2 IN THE ELECTRICAL SPECIFICATIONS |
| REFERENCING THE LATEST EDITION OF THE NEC, WHICH IS |
| 2008, IS INCORRECT.THE 2005 NEC WAS ADOPTED BY THE |
| FLORIDA LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE |
| APPLICATION FOR THIS PROJECT WAS AFTER THAT DATE AND |
| THE PLANS ARE SUBJECT TO THAT CODE. PLEASE CHANGE ALL |
| NOTES TO REFLECT THIS CHANGE. |
| |
| 4} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL |
| INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG |
| WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA |
| ADMINISTRATIVE CODE. |
| |
| 5} THE FLOOR PLAN LOCATES THE EXISTING ELECTRICAL |
| SERVICE, INDICATE IF THE NEW SERVICE IS TO BE INSTALLED |
| IN THE SAME LOCATION. |
| |
| 6} THE SCOPE OF WORK ON THE APPLICATION INDICATES NEW |
| PANELS IN BAY'S 2 AND 6. PANELS "B" AND "F" WHICH SERVE |
| THOSE BAYS ARE MARKED "EX SERVICE" ON THE PLAN, PLEASE |
| CLARIFY. |
| |
| 7} ALL THE PANELS ON THE FLOOR PLAN ARE MARKED PANEL |
| "A", CORRELATE WITH THE RISER DIAGRAM. |
| |
| 8} VERIFY THAT THE 3/0 FEEDERS SHOWN FOR 150 AMP LOADS |
| ARE CORRECT, ALSO VERIFY THE #2 EQUIPMENT GROUND IS |
| INTENDED TO BE RAN TO PANEL "F", ALTHOUGH NOT A |
| VIOLATION IF IT IS REQUIRED BY THE ENGINEER ON THE PLAN |
| IT MUST BE INSTALLED IN THE FIELD OR A REVISION IS |
| REQUIRED IF CHANGED AT A LATER DATE. SEE 250.66 FOR |
| REQUIRED SIZE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |