Plan Review Notes
Plan Review Notes For Permit 08070195
Permit Number 08070195
Review Stop B
Sequence Number 3
Notes
Date Text
2009-05-19 10:11:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SHEETS D1, A2, A3 ARE NOT IN THE RESUBMITTED SET.
 SEE FBC*106, MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS. BASED ON PREVIOUS COMMENTS, THE
 EXISTING FLOOR PLAN AND ELEVATIONS WERE CONTAINED IN
 THESE SHEETS. PLEASE PROVIDE THE MISSING PLAN SHEETS.
  
 2. SEE PREVIOUS LISTS, ITEMS 7 AND 12. A4, "GLASS BLK
 DETAIL" STATES "NON BEARING" BUT NO INFORMATION SHOWN
 AS TO HOW GRAVITY LOADS WILL BE PREVENTED FROM BEARING
 ON THE GLASS BLOCK, FBC2110.4.1. PLEASE EXPLAIN HOW
 THIS IS NON BEARING WHEN THE DETAIL SHOWS CONCRETE
 BLOCK ON TOP OF GLASS BLOCK.
  
 3. THERE IS A DETAIL ON SHEET A4 MARKED A-A3 LABELED
 "TYPICAL 4" PARTITION." THIS SPECIFIES WOOD, SHEET A1
 SPECIFIES METAL PARTITION WALLS. FBC*106, DETAILS
 SHOULD INCLUDE ENOUGH CONSISTENT INFORMATION TO
 DETERMINE SCOPE OF WORK.
  
  
  