Plan Review Notes
Plan Review Notes For Permit 08070195
Permit Number 08070195
Review Stop P
Sequence Number 2
Notes
Date Text
2009-01-09 09:39:43PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 ***FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHEET A1 PROPOSED FLOOR PLAN DOES NOT HAVE ANY
 INDICATION OF THE REQUIRED SERVICE SINK (EXISTING OR
 PROPOSED). PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER
 OF REQUIRED PLUMBING FIXTURES, OCCUPANCY A-3.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 5. OK
 6. OK
  
 7. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: PER FBC-
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.17.3.
 (1) THE STANDARD RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH
 LAVATORY TO BE NOT LESS THAT 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 (SEE FIGURE 30(A) AND FIGURE 30(E) AND TO
 COMPLY WITH SECTION 11-4,19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
 (2) THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 8. SHEET A3 (NOW A4) HC LAV. BATH PLAN VIEW DETAIL:
 PLEASE CORRECT AND CORRELATE THE SIDE WALL MEASUREMENTS
 WITH THE HC LAV. ELEVATION DETAIL. WATER CLOSET SHALL
 BE 1'6" AND THE LAVATORY SHALL BE 1'5". PER FBC-
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.16.2 FOR THE WATER CLOSET AND SECTION 11-4.19.3
 CLEAR FLOOR SPACE. ALSO PLEASE PROVIDE THE FOLOWING
 INFORMATION ON THE ELEVATION DETAILS AND SHEET A1
 PROPOSED FLOOR PLAN.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRES THE
 FOLLOWING INFORMATION AND CLEAR FLOOR SPACES NEEDS TO
 BE INDICATED ON SHEET A1).
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.5
 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" HIGH.
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRES THE FOLLOWING INFORMATION AND CLEAR FLOOR
 SAPCE TO BE INDICATED ON SHEET A1).
 11-4.19.3 CLEAR FLOOR SPACE. 30" X 48" SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32).
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 ****NO RESPONSE, CLEAR FLOOR SPACE FOR THE W/C'S AND
 THE LAVS AS WELL AS THE LAV FAUCET REQUIREMENTS WERE
 NOT ADDRESSED.
  
 9. SHEET A3 (NOW A4) TYPICAL BASE CABINET DETAIL
 INDICATES A KOHLER STAINLESS STEEL, LYRIC BAR SINK
 K-3288 W/GOOSENECK FAUCET K-11930 FOR ELEV. D ONLY.
 REUSED EXISTING SINK FOR ELEV. C ONLY. THIS DETAIL IS
 CONFUSING, PLEASE CLEARLY INDICATE THE ROOM NUMBER THIS
 SINK AND FAUCET IS BEING INSTALLED IN AND ITS LOCATION
 ON SHEET A1 FLOOR PLAN.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 10. SHEET A3 (NOW A4) DRINKING FOUNTAIN DETAIL: PLEASE
 PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE
 ELEVATION DETAIL AND INDICATE THE CLEAR FLOOR SPACE ON
 SHEET A1 PROPOSED FLOOR PLAN.
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRES THE FOLLOWING INFORMATION):
 11-4.15.2 SPOUT HIEGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM. (DETAIL INDICATES 36" TO DRINKING FOUNTAIN RIM
 NOT THE SPOUT).
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" CLEAR
 FLOOR SPACE.
 ****RESPONSE NOTED, BUT THE SPOUT HEIGHT AND THE CLEAR
 FLOOR SPACE HAVE NOT BEEN ADDRESSED. (NOTE: CLEAR FLOOR
 SPACE SHALL BE FORWARD APPROACH).
  
 11. SHEET A1 PROPOSED FLOOR PLAN MENS BATH #103
 INDICATES TWO (2) URINALS. PER FBC-CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE ONE OF THE URINALS SHALL BE
 COMPLIANT TO THE FOLLOWING SECTIONS:
  
 **11-4.18 URINALS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION AND INDICATE THE CLEAR FLOOR
 SPACE ON SHT A1 PROPOSED FLOOR PLAN)
 11-4.18.2 HEIGHT. RIM MAXIMUM 17" A.F.F.
 11-4.18.3 CLEAR FLOOR SPACE. 30" X 48"
 11-4.18.4 FLUSH CONTROLS. MAXIMUM 44" A.F.F.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 12. SHEET A1 PROPOSED FLOOR PLAN PLEASE PROVIDE THE
 FOLOWING REQUIREMENTS FOR TOILET ROOMS #103, #106, #109
 AND #110 PER FBC-CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE.
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" UNOBSTRUCTED
 CLEAR FLOOR SPACE (PER 11-4.2.3).
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 13. SHEET M1 SANITARY PLUMBING RISER DOES NOT REFLECT
 THE FLOOR PLAN. AT A MINIMUM THE RISER DIAGRAM SHALL
 REFLECT THE FLOOR PLAN. PLEASE CORRECT THE FOLLOWING
 AND PROVIDE A PLAN VIEW OF THE UNDERGROUND PLUMBING.
 PER FBC- PLUMBING SECTION 701.1 SCOPE.
 E} NOTE: REQUIRED SERVICE SINK NEEDS TO BE INDICATED ON
 THE PROPOSED FLOOR PLAN ON SHEET A1 AND ON THE RISER
 DIAGRAM ON SHEET M1
 ****NO RESPONSE, COMMENT SECTION E} NOT ADDRESSED.
 (RISER NOW INDICATED ON SHEET P1).
  
 14. OK
  
 15. SHEET M1 THE SANITARY PLUMBING RISER DIAGRAM NEEDS
 THE PRINTED NAME AND SIGNATURE: (OF THE PERSON
 DESIGNING THE RISER DIAGRAM)
 NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA
 BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED
 NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL
 SIGNATURE AND DATE ON SUCH INFORMATION. PER SECTION
 *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND THE DATE TO SAID DRAWINGS. PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 16. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3,
 PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER
 RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, LOCATIONS OF THE WATER SUPPLY LINE
 WITH BACKFLOW PREVENTER **608, THERMAL EXPANSION
 CONTROL FOR THE WATER HEATER **607.3, AND THE LOCATION
 OF THE WATER-HAMMER ARRESTORS WHERE QUICK CLOSING
 VALVES ARE UTILIZED. (EXAMPLES=WASH MACHINES,
 DISHWASHERS, ICE MAKERS) **604.9.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 17. THE SUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE
 DUE TO NOTHING ENTERED FOR WATER HEATER OR PIPING
 INSULATION COMPLIANCE. PER FBC- CHAPTER 13, SECTION
 13-412 WATER HEATING SYSTEMS TABLE 13-142.1.ABC.3
 PERFORMANCE REQUIREMENTS FOR WATER HEATING EQUIPMENT,
 AND TABLE 13-411.1.ABC.2 MINIMUM PIPE INSULATION.
  
 ***********NEW COMMENT***********
  
 1B. SHT C-1 REQUIRED PLUMBING FIXTURES. PER TABLE 403.1
 A-3 ASSEMBLY SHOWS THE REQUIRED W/C COUNT TO BE 1 PER
 150 FOR MALE AND 1 PER 75 FOR FEMALE WHICH COMES OUT TO
 1 FOR THE MALE AND 2 FOR THE FEMALE. (TOTAL OCCUPANCY
 195 DIVIDED BY 2 EQUALS 97.5 ROUNDED UP TO 98 MALE & 98
 FEMALE). PLEASE CORRECT REQUIRED PLUMBING FIXTURE
 COUNT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved