Date |
Text |
2009-01-09 09:39:43 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| ***FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| |
| 4. SHEET A1 PROPOSED FLOOR PLAN DOES NOT HAVE ANY |
| INDICATION OF THE REQUIRED SERVICE SINK (EXISTING OR |
| PROPOSED). PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER |
| OF REQUIRED PLUMBING FIXTURES, OCCUPANCY A-3. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 5. OK |
| 6. OK |
| |
| 7. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: PER FBC- |
| CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION |
| 11-4.17.3. |
| (1) THE STANDARD RESTROOM STALL SHALL CONTAIN AN |
| ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH |
| LAVATORY TO BE NOT LESS THAT 19 INCHES WIDE BY 17 |
| INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL |
| MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO |
| OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION |
| 11-4.17 (SEE FIGURE 30(A) AND FIGURE 30(E) AND TO |
| COMPLY WITH SECTION 11-4,19 OF THE CODE. SUCH |
| LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED |
| FIXTURE COUNT FOR THE BUILDING. |
| (2) THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE |
| CORNER, DIAGONAL TO THE DOOR. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 8. SHEET A3 (NOW A4) HC LAV. BATH PLAN VIEW DETAIL: |
| PLEASE CORRECT AND CORRELATE THE SIDE WALL MEASUREMENTS |
| WITH THE HC LAV. ELEVATION DETAIL. WATER CLOSET SHALL |
| BE 1'6" AND THE LAVATORY SHALL BE 1'5". PER FBC- |
| CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION |
| 11-4.16.2 FOR THE WATER CLOSET AND SECTION 11-4.19.3 |
| CLEAR FLOOR SPACE. ALSO PLEASE PROVIDE THE FOLOWING |
| INFORMATION ON THE ELEVATION DETAILS AND SHEET A1 |
| PROPOSED FLOOR PLAN. |
| |
| **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRES THE |
| FOLLOWING INFORMATION AND CLEAR FLOOR SPACES NEEDS TO |
| BE INDICATED ON SHEET A1). |
| 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.5 |
| FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" HIGH. |
| |
| **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL |
| REQUIRES THE FOLLOWING INFORMATION AND CLEAR FLOOR |
| SAPCE TO BE INDICATED ON SHEET A1). |
| 11-4.19.3 CLEAR FLOOR SPACE. 30" X 48" SHALL EXTEND A |
| MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE |
| 32). |
| 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND |
| ELECTRONICALLY CONTROLLED ARE EXAMPLES. |
| ****NO RESPONSE, CLEAR FLOOR SPACE FOR THE W/C'S AND |
| THE LAVS AS WELL AS THE LAV FAUCET REQUIREMENTS WERE |
| NOT ADDRESSED. |
| |
| 9. SHEET A3 (NOW A4) TYPICAL BASE CABINET DETAIL |
| INDICATES A KOHLER STAINLESS STEEL, LYRIC BAR SINK |
| K-3288 W/GOOSENECK FAUCET K-11930 FOR ELEV. D ONLY. |
| REUSED EXISTING SINK FOR ELEV. C ONLY. THIS DETAIL IS |
| CONFUSING, PLEASE CLEARLY INDICATE THE ROOM NUMBER THIS |
| SINK AND FAUCET IS BEING INSTALLED IN AND ITS LOCATION |
| ON SHEET A1 FLOOR PLAN. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 10. SHEET A3 (NOW A4) DRINKING FOUNTAIN DETAIL: PLEASE |
| PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE |
| ELEVATION DETAIL AND INDICATE THE CLEAR FLOOR SPACE ON |
| SHEET A1 PROPOSED FLOOR PLAN. |
| **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| (ELEVATION DETAIL REQUIRES THE FOLLOWING INFORMATION): |
| 11-4.15.2 SPOUT HIEGHT. SPOUT HEIGHT 36" TO OUTLET |
| MAXIMUM. (DETAIL INDICATES 36" TO DRINKING FOUNTAIN RIM |
| NOT THE SPOUT). |
| 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" CLEAR |
| FLOOR SPACE. |
| ****RESPONSE NOTED, BUT THE SPOUT HEIGHT AND THE CLEAR |
| FLOOR SPACE HAVE NOT BEEN ADDRESSED. (NOTE: CLEAR FLOOR |
| SPACE SHALL BE FORWARD APPROACH). |
| |
| 11. SHEET A1 PROPOSED FLOOR PLAN MENS BATH #103 |
| INDICATES TWO (2) URINALS. PER FBC-CHAPTER 11, FLORIDA |
| ACCESSIBILITY CODE ONE OF THE URINALS SHALL BE |
| COMPLIANT TO THE FOLLOWING SECTIONS: |
| |
| **11-4.18 URINALS (ELEVATION DETAIL REQUIRED WITH THE |
| FOLLOWING INFORMATION AND INDICATE THE CLEAR FLOOR |
| SPACE ON SHT A1 PROPOSED FLOOR PLAN) |
| 11-4.18.2 HEIGHT. RIM MAXIMUM 17" A.F.F. |
| 11-4.18.3 CLEAR FLOOR SPACE. 30" X 48" |
| 11-4.18.4 FLUSH CONTROLS. MAXIMUM 44" A.F.F. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 12. SHEET A1 PROPOSED FLOOR PLAN PLEASE PROVIDE THE |
| FOLOWING REQUIREMENTS FOR TOILET ROOMS #103, #106, #109 |
| AND #110 PER FBC-CHAPTER 11, FLORIDA ACCESSIBILITY CODE |
| SECTIONS. |
| 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR |
| SPACE. |
| 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE |
| SHALL BE 180-DEGREE WITH A MINIMUM 60" UNOBSTRUCTED |
| CLEAR FLOOR SPACE (PER 11-4.2.3). |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 13. SHEET M1 SANITARY PLUMBING RISER DOES NOT REFLECT |
| THE FLOOR PLAN. AT A MINIMUM THE RISER DIAGRAM SHALL |
| REFLECT THE FLOOR PLAN. PLEASE CORRECT THE FOLLOWING |
| AND PROVIDE A PLAN VIEW OF THE UNDERGROUND PLUMBING. |
| PER FBC- PLUMBING SECTION 701.1 SCOPE. |
| E} NOTE: REQUIRED SERVICE SINK NEEDS TO BE INDICATED ON |
| THE PROPOSED FLOOR PLAN ON SHEET A1 AND ON THE RISER |
| DIAGRAM ON SHEET M1 |
| ****NO RESPONSE, COMMENT SECTION E} NOT ADDRESSED. |
| (RISER NOW INDICATED ON SHEET P1). |
| |
| 14. OK |
| |
| 15. SHEET M1 THE SANITARY PLUMBING RISER DIAGRAM NEEDS |
| THE PRINTED NAME AND SIGNATURE: (OF THE PERSON |
| DESIGNING THE RISER DIAGRAM) |
| NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA |
| BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED |
| NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL |
| SIGNATURE AND DATE ON SUCH INFORMATION. PER SECTION |
| *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, |
| THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| SIGNATURE AND THE DATE TO SAID DRAWINGS. PER FLORIDA |
| STATUTES 481 AND 471 RESPECTIVELY. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 16. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3, |
| PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER |
| RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR |
| BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES, |
| VALVE LOCATIONS, LOCATIONS OF THE WATER SUPPLY LINE |
| WITH BACKFLOW PREVENTER **608, THERMAL EXPANSION |
| CONTROL FOR THE WATER HEATER **607.3, AND THE LOCATION |
| OF THE WATER-HAMMER ARRESTORS WHERE QUICK CLOSING |
| VALVES ARE UTILIZED. (EXAMPLES=WASH MACHINES, |
| DISHWASHERS, ICE MAKERS) **604.9. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 17. THE SUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE |
| DUE TO NOTHING ENTERED FOR WATER HEATER OR PIPING |
| INSULATION COMPLIANCE. PER FBC- CHAPTER 13, SECTION |
| 13-412 WATER HEATING SYSTEMS TABLE 13-142.1.ABC.3 |
| PERFORMANCE REQUIREMENTS FOR WATER HEATING EQUIPMENT, |
| AND TABLE 13-411.1.ABC.2 MINIMUM PIPE INSULATION. |
| |
| ***********NEW COMMENT*********** |
| |
| 1B. SHT C-1 REQUIRED PLUMBING FIXTURES. PER TABLE 403.1 |
| A-3 ASSEMBLY SHOWS THE REQUIRED W/C COUNT TO BE 1 PER |
| 150 FOR MALE AND 1 PER 75 FOR FEMALE WHICH COMES OUT TO |
| 1 FOR THE MALE AND 2 FOR THE FEMALE. (TOTAL OCCUPANCY |
| 195 DIVIDED BY 2 EQUALS 97.5 ROUNDED UP TO 98 MALE & 98 |
| FEMALE). PLEASE CORRECT REQUIRED PLUMBING FIXTURE |
| COUNT. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |
| |