Plan Review Notes
Plan Review Notes For Permit 08070195
Permit Number 08070195
Review Stop M
Sequence Number 2
Notes
Date Text
2009-01-10 17:51:53REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE EQUIPMENT SCHEDULE ON THE PLANS INDICATES THE
 SYSTEMS ARE "13 SEER." THIS IS NOT POSSIBLE AS SYSTEMS
 OF THIS SIZE ARE NOT GIVEN A "SEER" RATING. THE
 DOCUMENTATION PROVIDED FOR THE SELECTED EQUIPMENT
 INDICATES THAT THE EFFICIENCY RATING IS 9.1 EER.
 HOWEVER, PLANS INDICATE 7.5 TON SYSTEMS WHILE THE
 MANUFACTURER'S DATA IS FOR A 10 TON SYSTEM. PLEASE
 COORDINATE EQUIPMENT SCHEDULE, EFFICIENCY RATING AND
 THE DOCUMENTATION PROVIDED TO DEMONSTRATE CODE
 COMPLIANCE.
  
 2. ELECTRICAL PLANS INDICATE THAT THE A/C UNITS ARE
 EXISTING WHILE MECHANICAL DOCUMENTATION INDICATES THAT
 AC UNITS ARE NEW. ALSO, ELECTRICAL PLAN SHOWS ONE AHU
 AND ONE CU IN DIFFERENT LOCATIONS THAN THE MECHANICAL
 PLANS. PLEASE COORDINATE ELECTRICAL PLANS AND
 MECHANICAL PLANS IN ACCORDANCE WITH FBCB 106.1.1.
  
 3. PROVIDE OUTSIDE AIR CALCULATIONS BASED ON THE
 OCCUPANCY CLASSIFICATION AND OCCUPANT LOADS AS
 INDICATED IN FBCM TABLE 403.3. SHOW THE TOTAL REQUIRED
 CFM FOR EACH SYSTEM. ALSO, PROVIDE SHUTOFF DAMPER
 CONTROLS FOR THE OUTSIDE AIR DUCTS IN ACCORDANCE WITH
 FBCB 13-409.1.ABC.3.2.
  
 4. THE TWO RESTROOMS ON THE NORTH END OF THE SPACE ARE
 SHOWN WITH 50 CFM EXHAUST FANS. THE MINIMUM REQUIRED
 EXHAUST FOR THESE ROOMS IS 50 CFM PER WATER CLOSET OR
 URINAL IN ACCORDANCE WITH FBCM TABLE 403.3. THAT MEANS
 A MINIMUM OF 150 CFM IS REQUIRED FOR EACH RESTROOM.
  
 5. MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM 301.13.
 PROVIDE DETAIL WITH WIND LOAD CALCULATIONS FOR THE
 OUTDOOR INSTALLATION OF NEW CONDENSING UNITS SHOWING
 HOW THESE UNITS ARE TO BE INSTALLED TO RESIST
 ANTICIPATED WIND PRESSURES.
  
 6. EACH OF THE PROPOSED AC SYSTEMS IS DESIGNED TO
 PROVIDE IN EXCESS OF 2000 CFM. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM IN THE SUPPLY AIR DUCT IN
 ACCORDANCE WITH FBCM 606.2.1.
  
 7. ACCORDING TO PAGE C1 THIS BUILDING IS DESIGNED AND
 INTENDED FOR AN OCCUPANCY OF 195 PERSONS. THIS MEANS
 THE AIR CONDITIONING SYSTEM MUST BE DESIGNED BY A
 PROFESSIONAL ENGINEER IN ACCORDANCE WITH FLORIDA
 STATUTE 471.003(2)(H)(C). THIS PROJECT DOES NOT QUALIFY
 FOR THE EXCEPTION ALLOWING THE CONTRACTOR TO ACT AS THE
 DESIGNER. PLEASE PROVIDE PLANS DESIGNED BY A
 PROFESSIONAL ENGINEER IN ACCORDANCE WITH THIS STATUTE
 AND FBCB 105.3.1.2.
  