 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE AIR HANDLING UNITS ON SHEET E1 ARE CALCULATE
 WITH 10KW HEAT STRIPS. SHEET M1 INDICATES THE UNITS ARE
 15KW. CORRELATE SAME. THE CHANGE MUST BE REFLECTED IN
 THE LOAD CALCULATIONS.
  
 2} LIST THE VOLTAGE OF THE SERVICE ON THE RISER
 DIAGRAM. 215.5 NOTE: 240 VOLTS IS LISTED IN THE LOAD
 CALCULATION
  
 3} THE CHAIR LIFT IS CIRCUITED ON 15,16 AT THE DEVICE.
 THOSE CIRCUITS ARE LISTED AS A/C #2 (AS ARE 18, 19, 20)
 IN THE PANEL SCHEDULE.CORRELATE THE CIRCUITING. 408.4
 NEC.
  
 4} THE CHAIR LIFT IS NOT IN THE LOAD CALCULATIONS.
 220.14(A) SPECIFIC APPLIANCES OR LOADS AN OUTLET FOR A
 SPECIFIC APPLIANCE OR OTHER LOAD NOT COVERED IN
 220.14(B) THROUGH (L) SHALL BE CALCULATED BASED ON THE
 AMPERE RATING OF THE APPLIANCE OR LOAD SERVED.
  
 5} ONE WATER HEATER IS LABELED 12,13 AT THE RECEPTACLE
 NOT IN THE SCHEDULE. THE OTHER HEATER IS NOT LABELED.
 408.4
  
 6} CIRCUITS 3, 5, 6, 7, 8 ARE LABELED "RECEPTACLES BUT
 ARE LIGHTING CIRCUITS. CIRCUIT 10 IS LABELED LIGHTING
 AND IS A RECEPTACLE CIRCUIT. CORRECT THE PANEL
 SCHEDULE. 408.4 NEC.
  
 COMMENTS FROM THE PREVIOUS REVIEW WITH COMMENT NUMBER
 FROM SAME.***INDICATES FURTHER EXPLANATION OF PREVIOUS
 COMMENT
  
 6} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE
 SAME ON PLANS.***THE WALL UNITS ARE NOT CONNECTED TO
 THE LOCAL CIRCUIT PER 700.12(F)(4).
  
 7} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
  
 8} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.*** NO SIGNATURE ON THE PLANS.
  
 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63.AND LIGHT PER 210.70(A)
 (3) IF APPLICABLE.*** ONLY ONE AHU IS ON THE PLAN..
 .
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  