 BUILDING PLAN REVIEW
 PERMIT: 08070195
 ADD: 2000 6 AE ISAACS AVE
 CONT: NEWBOLD CONST.
 TEL: (561)842-0033
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS0
  
 12-29-08
 REVIEW: 2ND
 ACTION: DENIED
  
 **NOTE: SHEET D1 WHICH SHOWED THE EXISTING FLOOR PLAN
 AND ALL AREAS TO BE DEMOED WAS NOT RESUBMITTED ALONG
 WITH SHEET A2. AN EXISTING AND A PROPOSED PLAN ARE
 REQUIRED TO SHOW ALL CHANGES TO THE LAYOUT OF THE
 EXISTING BUILDING.**
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) OK
 3) OK
 4) OK
 5) OK
  
 6) SHEET A1 SHOWS TWO NEW WINDOW OPENINGS AT THE NORTH
 ELEVATION, HOWEVER SHEET A2 SHOWS THREE WINDOWS. WILL
 THERE BE THREE OR TWO WINDOWS. THE SOUTH ELEVATION ON
 SHEET D1- A1 AND A2 HAVE CONFLICTING INFORMATION AS TO
 HOW MANY WINDOWS WILL BE CHANGED OUT. WHAT TYPES OF
 WINDOWS ARE INSTALLED AT THIS LOCATION? REMEMBER AN
 EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE
 ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE OR
 ENERGY EFFICIENT THAN ITS EXISTING CONDITION. FBC
 (EXISTING) 501.2.
  
 **NO RESPONSE NOT ADDRESSED**
 7) 106.3.3* PRODUCT APPROVALS- 2004THOSE PRODUCTS THAT
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE PRODUCT
 APPROVAL FOR THE NEW GLASS BLOCK. SHEET A4 GLASS BLOCK
 DETAIL FAILS TO STATE THE TYPE OF GLASS UNIT, THE SIZE,
 THE LATERAL AND VERTICAL SUPPORT. THE HEADER ABOVE THE
 GLASS UNITS SHOWS A BLOCK WALL. GLASS UNIT MASONRY
 PANELS SHALL BE ISOLATED SO THAT IN-PLANE LOADS ARE NOT
 IMPARTED ON THE UNITS FBC 2110.4.1. THE DETAIL SHALL
 STATE THE VERTICAL AND LATERAL SUPPORTS FBC 2110.4.3.
 PLEASE SEE SECTION 2110.7 FOR INFORMATION REGARDING THE
 REINFORCEMENT OF THE GLASS UNITS. FOR ADDITIONAL
 INFORMATION SEE SECTION FBC 2110. IF THE GLASS BLOCK
 UNITS ARE NOT IMPACT RESISTANT, IMPACT PROTECTION SHALL
 BE PROVIDED FBC 1609.1.4. PROVIDE PRODUCT APPROVAL FOR
 THE HURRICANE PROTECTION (SHUTTERS).
  
 8) OK
  
 **NO RESPONSE NOT ADDRESSED**
 9) SHEET A1, THE WALL LEGEND INDICATES THAT A PORTION
 OF THE EXISTING STRUCTURE WILL BE CONSTRUCTED WITH 4
 INCH WOOD STUDS; IF THAT IS THE CASE INDICATE THE
 EXTERIOR WALL COVERINGS WITH A COMPLETE ELEVATION WALL
 DETAIL SHOWING ALL MATERIALS. THE WALL LEGEND HAS NO
 SYMBOL FOR THE NEW CONSTRUCTED WALLS. IF SOME WALLS ARE
 DIFFERENT IN SIZE LIKE THE ONE SEPARATING THE BATHROOMS
 AT THE DRESSING ROOMS; INDICATE THE SIZE OF THE WALL
 AND THE MATERIALS TO BE USED ON THE WALL DETAIL SHEET
 A3. ADDITIONAL INFORMATION IS REQUIRED 106.1.2
  
 **SEE THE CODE SECTIONS MENTION BELOW AND SHOW
 COMPLIANCE**
 10) THE ACCESSIBLE BATHROOMS NEED TO BE IN COMPLIANCE
 WITH SECTION FBC 11-4.16 / 11-4.17 / 11-4.18 AND
 11-4.19. THE GRAB RAILS FOR THE BATHROOM SHOWN ON THE
 FLOOR PLAN DO NOT MATCH THE ONE ON THE DETAIL SHEET.
 SEE NOTES ON PLANS AND MAKE THE REQUIRED CHANGES.
  
 **NOTED; HOWEVER, THE NEW DETAIL ON SHEET A1 FOR THE
 STAIRS FAIL TO CLEARLY SHOW THE RISE AND TREAD DEPTH OF
 THE STAIRS...
 11) SHEET D1 INDICATES THE ALTERATION TO THE EXISTING
 EXTERIOR STAIRS AT THE SOUTH ELEVATION; HOWEVER, NO
 CONSTRUCTION DETAIL IS PROVIDED SHOWING THE SIZE OF THE
 TREADS AND RISERS. THE STAIRS SHALL BE IN COMPLIANCE
 WITH FBC 1009 AND 11-4.9. SHEET A3 SOUTH ELEVATION
 HANDRAIL SHALL BE IN CONFORMANCE WITH FBC 1012.3, SUCH
 THAT A 4 INCH DIAMETER SPHERE CANNOT PASS THROUGH ANY
 OPENING UP TO A HEIGHT OF 34 INCHES. SHOW THE DIMENSION
 BETWEEN THE LANDING AND THE BOTTOM OF THE RAIL.
  
 **NO RESPONSE NOT ADDRESSED**
 12) THE DRAWINGS NEED TO SHOW THE HEAD AND SILL DETAIL
 FOR THE NEW OPENINGS. PROVIDE THE FRONT ELEVATION
 DETAIL FOR THE NEW OPENINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER