| BUILDING PLAN REVIEW |
| PERMIT: 08070195 |
| ADD: 2000 6 AE ISAACS AVE |
| CONT: NEWBOLD CONST. |
| TEL: (561)842-0033 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS0 |
| |
| 12-29-08 |
| REVIEW: 2ND |
| ACTION: DENIED |
| |
| **NOTE: SHEET D1 WHICH SHOWED THE EXISTING FLOOR PLAN |
| AND ALL AREAS TO BE DEMOED WAS NOT RESUBMITTED ALONG |
| WITH SHEET A2. AN EXISTING AND A PROPOSED PLAN ARE |
| REQUIRED TO SHOW ALL CHANGES TO THE LAYOUT OF THE |
| EXISTING BUILDING.** |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) OK |
| 3) OK |
| 4) OK |
| 5) OK |
| |
| 6) SHEET A1 SHOWS TWO NEW WINDOW OPENINGS AT THE NORTH |
| ELEVATION, HOWEVER SHEET A2 SHOWS THREE WINDOWS. WILL |
| THERE BE THREE OR TWO WINDOWS. THE SOUTH ELEVATION ON |
| SHEET D1- A1 AND A2 HAVE CONFLICTING INFORMATION AS TO |
| HOW MANY WINDOWS WILL BE CHANGED OUT. WHAT TYPES OF |
| WINDOWS ARE INSTALLED AT THIS LOCATION? REMEMBER AN |
| EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE |
| ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE OR |
| ENERGY EFFICIENT THAN ITS EXISTING CONDITION. FBC |
| (EXISTING) 501.2. |
| |
| **NO RESPONSE NOT ADDRESSED** |
| 7) 106.3.3* PRODUCT APPROVALS- 2004THOSE PRODUCTS THAT |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE PRODUCT |
| APPROVAL FOR THE NEW GLASS BLOCK. SHEET A4 GLASS BLOCK |
| DETAIL FAILS TO STATE THE TYPE OF GLASS UNIT, THE SIZE, |
| THE LATERAL AND VERTICAL SUPPORT. THE HEADER ABOVE THE |
| GLASS UNITS SHOWS A BLOCK WALL. GLASS UNIT MASONRY |
| PANELS SHALL BE ISOLATED SO THAT IN-PLANE LOADS ARE NOT |
| IMPARTED ON THE UNITS FBC 2110.4.1. THE DETAIL SHALL |
| STATE THE VERTICAL AND LATERAL SUPPORTS FBC 2110.4.3. |
| PLEASE SEE SECTION 2110.7 FOR INFORMATION REGARDING THE |
| REINFORCEMENT OF THE GLASS UNITS. FOR ADDITIONAL |
| INFORMATION SEE SECTION FBC 2110. IF THE GLASS BLOCK |
| UNITS ARE NOT IMPACT RESISTANT, IMPACT PROTECTION SHALL |
| BE PROVIDED FBC 1609.1.4. PROVIDE PRODUCT APPROVAL FOR |
| THE HURRICANE PROTECTION (SHUTTERS). |
| |
| 8) OK |
| |
| **NO RESPONSE NOT ADDRESSED** |
| 9) SHEET A1, THE WALL LEGEND INDICATES THAT A PORTION |
| OF THE EXISTING STRUCTURE WILL BE CONSTRUCTED WITH 4 |
| INCH WOOD STUDS; IF THAT IS THE CASE INDICATE THE |
| EXTERIOR WALL COVERINGS WITH A COMPLETE ELEVATION WALL |
| DETAIL SHOWING ALL MATERIALS. THE WALL LEGEND HAS NO |
| SYMBOL FOR THE NEW CONSTRUCTED WALLS. IF SOME WALLS ARE |
| DIFFERENT IN SIZE LIKE THE ONE SEPARATING THE BATHROOMS |
| AT THE DRESSING ROOMS; INDICATE THE SIZE OF THE WALL |
| AND THE MATERIALS TO BE USED ON THE WALL DETAIL SHEET |
| A3. ADDITIONAL INFORMATION IS REQUIRED 106.1.2 |
| |
| **SEE THE CODE SECTIONS MENTION BELOW AND SHOW |
| COMPLIANCE** |
| 10) THE ACCESSIBLE BATHROOMS NEED TO BE IN COMPLIANCE |
| WITH SECTION FBC 11-4.16 / 11-4.17 / 11-4.18 AND |
| 11-4.19. THE GRAB RAILS FOR THE BATHROOM SHOWN ON THE |
| FLOOR PLAN DO NOT MATCH THE ONE ON THE DETAIL SHEET. |
| SEE NOTES ON PLANS AND MAKE THE REQUIRED CHANGES. |
| |
| **NOTED; HOWEVER, THE NEW DETAIL ON SHEET A1 FOR THE |
| STAIRS FAIL TO CLEARLY SHOW THE RISE AND TREAD DEPTH OF |
| THE STAIRS... |
| 11) SHEET D1 INDICATES THE ALTERATION TO THE EXISTING |
| EXTERIOR STAIRS AT THE SOUTH ELEVATION; HOWEVER, NO |
| CONSTRUCTION DETAIL IS PROVIDED SHOWING THE SIZE OF THE |
| TREADS AND RISERS. THE STAIRS SHALL BE IN COMPLIANCE |
| WITH FBC 1009 AND 11-4.9. SHEET A3 SOUTH ELEVATION |
| HANDRAIL SHALL BE IN CONFORMANCE WITH FBC 1012.3, SUCH |
| THAT A 4 INCH DIAMETER SPHERE CANNOT PASS THROUGH ANY |
| OPENING UP TO A HEIGHT OF 34 INCHES. SHOW THE DIMENSION |
| BETWEEN THE LANDING AND THE BOTTOM OF THE RAIL. |
| |
| **NO RESPONSE NOT ADDRESSED** |
| 12) THE DRAWINGS NEED TO SHOW THE HEAD AND SILL DETAIL |
| FOR THE NEW OPENINGS. PROVIDE THE FRONT ELEVATION |
| DETAIL FOR THE NEW OPENINGS. |
| |