2008-07-14 17:08:04PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET C1 IS INDICATING THE WRONG OCCUPANCY AS GROUP
 B BUSSINESS. THE CORRECT OCCUPANCY GROUP SHOULD BE
 GROUP A-3 (PLACES OF WORSHIP AND OTHER RELIGIOUS
 SERVICES. CHURCHES WITHOUT ASSEMBLY HALLS). ALSO THE
 NUMBER OF OCCUPANTS NEEDS TO BE INDICATED. PER
 FBC-PLUMBING SECTION 403.1.
  
 2. SHEET C1: PLEASE DECLARE THE CORRECT GOVERNING CODE
 (FBC-2004 WITH 2007 REVISIONS). PER (W.P.B. AS AMENDED)
 SECTION 106.5 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 3. SHEET C1: PLEASE DECLARE THE LEVEL OF ALTERATION.
 PER FBC-2004 EXISTING BUILDING CODE.
  
 4. SHEET A1 PROPOSED FLOOR PLAN DOES NOT HAVE ANY
 INDICATION OF THE REQUIRED SERVICE SINK (EXISTING OR
 PROPOSED). PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER
 OF REQUIRED PLUMBING FIXTURES, OCCUPANCY A-3.
  
 5. SHEET A1 PROPOSED FLOOR PLAN: PLEASE CLEARLY
 IDENTIFY ALL PROPOSED PLUMBING FIXTURES ON THIS SHEET
 AND PROVIDE A FIXTURE SCHEDULE. SOME PLUMBING FIXTURES
 ARE NOT IDENTIFIED AND OTHERS ARE IDENTIFIED BY
 ABBREVIATIONS. IS THE WF. IN THE ENTRY A DRINKING
 FOUNTAIN? THE LAVATORIES ARE NOT IDENTIFIED AND SOME OF
 THE WATER CLOSETS HAVE ABB. IDENTIFICATION. PLEASE
 CLARIFY THIS PER FBC- PLUMBING SECTION 401.1 SCOPE.
  
 6. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: THE
 GRAB BARS ARE BEING INDICATED IN THE WRONG PLACE. THE
 36" GRAB BAR NEEDS TO BE LOCATED BEHIND THE WATER
 CLOSET AND THE 42" GRAB BAR NEEDS TO BE LOCATED TO THE
 SIDE. PER FBC- CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTION 11-4.16.4.
  
 7. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: PER
 FBC- CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.17.3.
 EXCEPTION: NEW CONSTRUCTION.
 (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
 (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER, DIAGONAL TO THE DOOR.
  
 8. SHEET A3 HC LAV. BATH PLAN VIEW DETAIL: PLEASE
 CORRECT AND CORRELATE THE SIDE WALL MEASUREMENTS WITH
 THE HC LAV. ELEVATION DETAIL. WATER CLOSET SHALL BE
 1'-6" AND THE LAVATORY SHALL BE 1'-5". PER FBC- CHAPTER
 11, FLORIDA ACCESSIBILITY CODE SECTION 11-4.16.2 FOR
 THE WATER CLOSET AND SECTION 11-4.19.3 CLEAR FLOOR
 SPACE. ALSO PLEASE PROVIDE THE FOLLOWING INFORMATION ON
 THE ELEVATION DETAILS AND SHEET A1 PROPOSED FLOOR
 PLAN.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRES THE
 FOLLOWING INFORMATION AND CLEAR FLOOR SPACE NEEDS TO BE
 INDICATED ON SHEET A1)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.5
 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" HIGH.
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRES THE FOLLOWING INFORMATION AND CLEAR FLOOR
 SPACE NEEDS TO BE INDICATED ON SHEET A1)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
  
 9. SHEET A3 TYPICAL BASE CABINET DETAIL INDICATES A
 KOHLER STAINLESS STEEL, LYRIC BAR SINK K-3288 W/GOOSE
 NECK FAUCET K-11930 FOR ELEV. D ONLY. REUSED EXISTING
 SINK FOR ELEV. C ONLY. THIS DETAIL IS CONFUSING, PLEASE
 CLEARLY INDICATE THE ROOM NUMBER THIS SINK ANS FAUCET
 IS BEING INSTALLED IN AND ITS LOCATION ON SHEET A1
 FLOOR PLAN.
  
 10. SHEET A3 DRINKING FOUNTAIN DETAIL: PLEASE PROVIDE
 THE FOLLOWING INFORMATION ON THE ELEVATION DETAIL AND
 INDICATE THE CLEAR FLOOR SPACE ON SHEET A1 PROPOSED
 FLOOR PLAN.
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRES WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM. (DETAIL INDICATES 36" TO DRINKING FOUNTAIN RIM
 NOT THE SPOUT)
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 11. SHEET A1 PROPOSED FLOOR PLAN MENS BATH #103
 INDICATES TWO (2) URINALS. PER FBC-CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE ONE OF THE URINALS SHALL BE
 COMPLIANT TO THE FOLLOWING SECTIONS.
  
 **11-4.18 URINALS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION AND INDICATE THE CLEAR FLOOR
 SPACE ON SHEET A1 PROPOSED FLOOR PLAN)
 11-4.18.2 HEIGHT. RIM MAXIMUM 17" A.F.F.
 11-4.18.3 CLEAR FLOOR SPACE. 30" X 48"
 11-4.18.4 FLUSH CONTROLS. MAXIMUM 44" A.F.F.
  
 12. SHEET A1 PROPOSED FLOOR PLAN PLEASE PROVIDE THE
 FOLLOWING REQUIREMENTS FOR BATHROOMS #103, #106, #109,
 AND #110 PER FBC-CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 13. SHEET M1 SANITARY PLUMBING RISER DOES NOT REFLECT
 THE FLOOR PLAN. AT A MINIMUM THE RISER DIAGRAM SHALL
 REFLECT THE FLOOR PLAN. PLEASE CORRECT THE FOLLOWING
 AND PROVIDE A PLAN VIEW OF THE UNDERGROUND PLUMBING.
 PER FBC- PLUMBING SECTION 701.1 SCOPE.
 A} DRINKING FOUNTAIN MISSING FROM RISER DIAGRAM.B}
 LAVATORY IN MENS BATH #103 BEING INDICATED IN WRONG
 PLACE.
 C} LAVATORY IN WOMENS BATH #106 HANDICAP STALL BING
 INDICATED IN WRONG PLACE.
 D} LAVATORIES IN MENS BATH #109 AND WOMENS BATH #110
 BEING INDICATED IN WRONG PLACE.
 E} NOTE: REQUIRED SERVICE SINK NEEDS TO BE INDICATED
 ON THE PROPOSED FLOOR PLAN ON SHEET A1 AND ON THE RISER
 DIAGRAM ON SHEET M1.
  
 14. SHEET M1 SANITARY PLUMBING RISER: THE FOLLOWING
 FIXTURES REQUIRE VENTS PER THE FOLLOWNG FBC- PLUMBING
 SECTIONS.
 A} URINALS IN MENS BATH #103. PER SECTION 901.2.1
 VENTING REQUIRED.
 B} A CIRCUIT VENT SHALL BE LOCATED BETWEEN THETWO MOST
 UPSTREAM FIXTURE DRAINS. PER SECTION 911.2 VENT
 CONNECTION.
  
 15. SHEET M1 THE SANITARY PLUMBING RISER DIAGRAM NEEDS
 THE PRINTED NAME AND SIGNATURE:
 NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA
 BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED
 NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL
 SIGNATURE AND DATE ON SUCH INFORMATION. PER SECTION
 *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 *ROLANDS A/C AND REFRIGERATION IS NOT A LICENSED
 PLUMBING CONTRACTOR AND MAY NOT DESIGN OR SIGN FOR THE
 SANITARY PLUMBING RISER. PER F.S. 471.003(H). PLEASE
 REMOVE PLUMBING FROM THE MECHANICAL PLAN AND SUBMIT
 SEPERATELY.
  
 16. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER
 RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH
 BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER **607.3, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE
 UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE
 MAKERS) **604.9.
  
 17. THE SUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE
 DUE TO NOTHING ENTERED FOR WATER HEATER OR PIPING
 COMPLIANCE. PER FBC- CHAPTER 13, SECTION 13-412 WATER
 HEATING SYSTEMS TABLE 13-412.1.ABC.3 PERFORMANCE
 REQUIREMENTS FOR WATER HEATING EQUIPMENT, AND TABLE
 13-411.1.ABC.2 MINIMUM PIPE INSULATION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER