2008-07-10 09:22:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) THE MEN BATH #103 AND WOMEN BATH #106 REQUIRE |
| EXHAUST FANS, PER 2004 FBC/M 402.3.1 AND TABLE 403.3. |
| PLEASE CORRECT. (SHOW ON MECHANICAL PLAN WITH CFM'S.) |
| |
| 2) PLEASE SHOW ON MECHANICAL PLANS ALL THE SUPPLY AND |
| RETURN AIR DUCT SIZES, PER 2004 FBC 106.3.5 (IF |
| EXISTING PLEASE LABEL AS EXISTING). |
| |
| 3) SHOW ON MECHANICAL PLAN HOW THE AIR IN THE MAIN HALL |
| IS RETURNING TO THE AIR HANDLER UNITS, PER 2004 FBC/M |
| 601.4. |
| |
| 4) IF THE AIR HANDLER UNITS ARE EXISTING PLEASE LABEL |
| AS EXISTING, IF NEW PROVIDE REQUIRED INFORMATION WITH |
| EQUIPMENT SCHEDULE, AND SHOW THE LOCATION OF THE |
| CONDENSER UNITS, PER 2004 FBC 106.3.5. |
| |
| 5) SHOW THE BATHROOM EXHAUST FANS (WITH CFM'S) FOR MEN |
| BATH #109 AND WOMEN BATH #110 ON THE MECHANICAL PLAN, |
| PER 2004 FBC/M 402.3.1 AND TABLE 403.3. |
| |
| 6) MECHANICAL PLAN M1 HAS A PLUMBING RISER DIAGRAM ON |
| IT, ROLAND'S A/C IS NOT A LICENSED PLUMBING CONTRACTOR |
| AND MAY NOT DESIGN PLUMBING RISERS. SEE F.S 471.003 |
| (H). PLEASE REMOVE FROM MECHANICAL PLAN. |
| |
| 7) THE MECHANICAL PLANS NEED THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND |
| CONTRACTORS LICENSE NUMBER ON THEM, SEE W.P.B. AMEND. |
| 106.1.3. |
| |
| *** BE ADVISED THE MECHANICAL CONTRACTOR WILL NEED TO |
| SIGN ON FOR THE MECHANICAL PERMIT BEFOR THE MECHANICAL |
| PLANS PASS REVIEW AS HE IS THE DESIGNER, SEE FS 471.003 |
| (H). |
| |