2008-07-10 09:22:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MEN BATH #103 AND WOMEN BATH #106 REQUIRE
 EXHAUST FANS, PER 2004 FBC/M 402.3.1 AND TABLE 403.3.
 PLEASE CORRECT. (SHOW ON MECHANICAL PLAN WITH CFM'S.)
  
 2) PLEASE SHOW ON MECHANICAL PLANS ALL THE SUPPLY AND
 RETURN AIR DUCT SIZES, PER 2004 FBC 106.3.5 (IF
 EXISTING PLEASE LABEL AS EXISTING).
  
 3) SHOW ON MECHANICAL PLAN HOW THE AIR IN THE MAIN HALL
 IS RETURNING TO THE AIR HANDLER UNITS, PER 2004 FBC/M
 601.4.
  
 4) IF THE AIR HANDLER UNITS ARE EXISTING PLEASE LABEL
 AS EXISTING, IF NEW PROVIDE REQUIRED INFORMATION WITH
 EQUIPMENT SCHEDULE, AND SHOW THE LOCATION OF THE
 CONDENSER UNITS, PER 2004 FBC 106.3.5.
  
 5) SHOW THE BATHROOM EXHAUST FANS (WITH CFM'S) FOR MEN
 BATH #109 AND WOMEN BATH #110 ON THE MECHANICAL PLAN,
 PER 2004 FBC/M 402.3.1 AND TABLE 403.3.
  
 6) MECHANICAL PLAN M1 HAS A PLUMBING RISER DIAGRAM ON
 IT, ROLAND'S A/C IS NOT A LICENSED PLUMBING CONTRACTOR
 AND MAY NOT DESIGN PLUMBING RISERS. SEE F.S 471.003
 (H). PLEASE REMOVE FROM MECHANICAL PLAN.
  
 7) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTORS LICENSE NUMBER ON THEM, SEE W.P.B. AMEND.
 106.1.3.
  
 *** BE ADVISED THE MECHANICAL CONTRACTOR WILL NEED TO
 SIGN ON FOR THE MECHANICAL PERMIT BEFOR THE MECHANICAL
 PLANS PASS REVIEW AS HE IS THE DESIGNER, SEE FS 471.003
 (H).
  