Plan Review Notes
Plan Review Notes For Permit 08070195
Permit Number 08070195
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-18 15:42:01***DENIED***
  
 1) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 2) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS.
  
 3) RATED DOOR TO BE PROVIDED WITH UL LISTED CLOSERS.
 PLEASE ADD TO DOOR SCHEDULE.
  
 4) NOTE ON LS SHEET REFERENCES FIRE EXTINGUISHERS.
 PLEASE SHOW LOCATIONS ON DRAWINGS.
  
 5) PLEASE CLARIFY OCCUPANCY CLASSIFICATION FOR
 BUILDING. PLEASE NOTE THAT MEANS OF EGRESS SHALL COMPLY
 WITH NFPA 101, CHAPTER 7 AND REQUIREMENTS FOR ASSEMBLY
 OCCUPANCIES NOT CHAPTER 38.
  
 6) STAIRS AND RAMPS TO COMPLY WITH NFPA 101, CHAPTER 7.
 SEE SEC. 7.2.5 FOR RAMPS AND 7.2.2 FOR STAIRS.
  
 7) SHOW NEW AND EXISTING ILLUMINATED EXITS SIGN AND
 EMERGENCY LIGHTING FACILITY LOCATIONS.
  
 8) PLEASE INDICATE OCCUPANT LOAD FOR BUILDING USING
 NFPA 101, TABLE 7.3.1.2 FOR CALCULATIONS.
  
 9) IS BUILDING PROTECTED BY FIRE PROTECTION SYSTEMS, IE
 FIRE SPRINKLER AND OR FIRE ALARM?
  
 10) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING IN TERMS OF CLASS A,B OR C.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN RECVIEW
 FIRE PREVENTION (561) 804-4756