Plan Review Notes For Permit 08070195 |
Permit Number |
08070195 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-18 15:42:01 | ***DENIED*** | | | | 1) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | 2) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR | | HANDRAILS AND GUARDS. | | | | 3) RATED DOOR TO BE PROVIDED WITH UL LISTED CLOSERS. | | PLEASE ADD TO DOOR SCHEDULE. | | | | 4) NOTE ON LS SHEET REFERENCES FIRE EXTINGUISHERS. | | PLEASE SHOW LOCATIONS ON DRAWINGS. | | | | 5) PLEASE CLARIFY OCCUPANCY CLASSIFICATION FOR | | BUILDING. PLEASE NOTE THAT MEANS OF EGRESS SHALL COMPLY | | WITH NFPA 101, CHAPTER 7 AND REQUIREMENTS FOR ASSEMBLY | | OCCUPANCIES NOT CHAPTER 38. | | | | 6) STAIRS AND RAMPS TO COMPLY WITH NFPA 101, CHAPTER 7. | | SEE SEC. 7.2.5 FOR RAMPS AND 7.2.2 FOR STAIRS. | | | | 7) SHOW NEW AND EXISTING ILLUMINATED EXITS SIGN AND | | EMERGENCY LIGHTING FACILITY LOCATIONS. | | | | 8) PLEASE INDICATE OCCUPANT LOAD FOR BUILDING USING | | NFPA 101, TABLE 7.3.1.2 FOR CALCULATIONS. | | | | 9) IS BUILDING PROTECTED BY FIRE PROTECTION SYSTEMS, IE | | FIRE SPRINKLER AND OR FIRE ALARM? | | | | 10) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | WALLS AND CEILING IN TERMS OF CLASS A,B OR C. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN RECVIEW | | FIRE PREVENTION (561) 804-4756 |
|