Plan Review Notes
Plan Review Notes For Permit 08070195
Permit Number 08070195
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-21 15:31:49 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE IS AN ELECTRICAL SHEET SUBMITTED BUT THE SCOPE
 OF WORK IS NOT CLEAR. INDICATE WHAT WORK IS EXISTING
 (IF ANY) AND WHAT IS TO BE INSTALLED UNDER THIS PERMIT.
  
 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1 FBC,
 PERFORMANCE CALCULATION PROCEDURES. SEE 13-415.2B OR
 13-415.2.C.1 DENSITIES.SUBMIT A LEGEND OF FIXTURE TYPES
 AND WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS
  
 3} METHOD ?A? ENERGY CALCULATIONS WERE SUBMITTED FOR
 THIS PROJECT. METHOD ?A? CAN BE USED FOR ?WHOLE
 BUILDINGS?. AS THIS IS AN ?EXISTING BUILDING ? BY
 DEFINITION?, FORM ?A? IS NEITHER REQUIRED OR ALLOWED.
 SEE 13-101.6. ALL THAT IS REQUIRED FOR THE ELECTRICAL
 REVIEW IS THE BASIC PRESCRIPTIVE REQUIREMENTS.
  
 4} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES.106.3.5 FBC.
  
 5} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 6} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE
 SAME ON PLANS.
  
 7} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
  
 8} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 9} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.UNDER 471.003 FS THE CONTRACTOR OF RECORD MAY
 DRAW THE DESIGN IF HE IS THE INSTALLER
  
 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63.AND LIGHT PER 210.70(A)
 (3) IF APPLIOCABLE..
 .
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718