2008-07-21 15:31:49 | |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS |
| AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THERE IS AN ELECTRICAL SHEET SUBMITTED BUT THE SCOPE |
| OF WORK IS NOT CLEAR. INDICATE WHAT WORK IS EXISTING |
| (IF ANY) AND WHAT IS TO BE INSTALLED UNDER THIS PERMIT. |
| |
| 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1 FBC, |
| PERFORMANCE CALCULATION PROCEDURES. SEE 13-415.2B OR |
| 13-415.2.C.1 DENSITIES.SUBMIT A LEGEND OF FIXTURE TYPES |
| AND WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN |
| THE CALCULATIONS |
| |
| 3} METHOD ?A? ENERGY CALCULATIONS WERE SUBMITTED FOR |
| THIS PROJECT. METHOD ?A? CAN BE USED FOR ?WHOLE |
| BUILDINGS?. AS THIS IS AN ?EXISTING BUILDING ? BY |
| DEFINITION?, FORM ?A? IS NEITHER REQUIRED OR ALLOWED. |
| SEE 13-101.6. ALL THAT IS REQUIRED FOR THE ELECTRICAL |
| REVIEW IS THE BASIC PRESCRIPTIVE REQUIREMENTS. |
| |
| 4} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| DEVICES.106.3.5 FBC. |
| |
| 5} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| PLAN. |
| |
| 6} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 |
| (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE |
| SAME ON PLANS. |
| |
| 7} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 |
| FBC AS AMENDED. |
| |
| 8} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER |
| 106.1.3.FBC. |
| |
| 9} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS |
| AMENDED.UNDER 471.003 FS THE CONTRACTOR OF RECORD MAY |
| DRAW THE DESIGN IF HE IS THE INSTALLER |
| |
| 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| 440.14, RECEPTACLE PER 210.63.AND LIGHT PER 210.70(A) |
| (3) IF APPLIOCABLE.. |
| . |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |