2008-08-12 10:57:39 | |
| BUILDING PLAN REVIEW |
| PERMIT: 08070195 |
| ADD: 2000 6 AE ISAACS AVE |
| CONT: NEWBOLD CONST. |
| TEL: (561)842-0033 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 3) SHEET C1. THE OCCUPANCY USE OF THE BUILDING |
| INDICATED ON THE DRAWINGS IS BUSINESS, HOWEVER, |
| ACCORDING TO THE USED INDICATED ON THE DRAWINGS THE |
| OCCUPANCY OF THE BUILDING WILL FALL UNDER THE CATEGORY |
| OF A-3. SEE FBC 303. |
| |
| 4) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 5) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. |
| |
| 6) SHEET A1 SHOWS TWO NEW WINDOW OPENINGS AT THE NORTH |
| ELEVATION, HOWEVER SHEET A2 SHOWS THREE WINDOWS. WILL |
| THERE BE THREE OR TWO WINDOWS. THE SOUTH ELEVATION ON |
| SHEET D1- A1 AND A2 HAVE CONFLICTING INFORMATION AS TO |
| HOW MANY WINDOWS WILL BE CHANGED OUT. WHAT TYPES OF |
| WINDOWS ARE INSTALLED AT THIS LOCATION? REMEMBER AN |
| EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE |
| ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE OR |
| ENERGY EFFICIENT THAN ITS EXISTING CONDITION. FBC |
| (EXISTING) 501.2. |
| |
| 7) 106.3.3* PRODUCT APPROVALS- 2004THOSE PRODUCTS THAT |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE PRODUCT |
| APPROVAL FOR THE NEW GLASS BLOCK. |
| |
| 8) IS THE BUILDING TRULY A 4 STORY BUILDING AS STATED |
| SHEET C1? INDICATE THE OCCUPANT LOAD OF THE BUILDING ON |
| THE PLANS PER FBC 1004 AND TABLE 1004.1.2. |
| |
| 9) SHEET A1, THE WALL LEGEND INDICATES THAT A PORTION |
| OF THE EXISTING STRUCTURE WILL BE CONSTRUCTED WITH 4? |
| WOOD STUDS; IF THAT IS THE CASE INDICATE THE EXTERIOR |
| WALL COVERINGS WITH A COMPLETE ELEVATION WALL DETAIL |
| SHOWING ALL MATERIALS. THE WALL LEGEND HAS NO SYMBOL |
| FOR THE NEW CONSTRUCTED WALLS. IF SOME WALLS ARE |
| DIFFERENT IN SIZE LIKE THE ONE SEPARATING THE BATHROOMS |
| AT THE DRESSING ROOMS; INDICATE THE SIZE OF THE WALL |
| AND THE MATERIALS TO BE USED ON THE WALL DETAIL SHEET |
| A3. ADDITIONAL INFORMATION IS REQUIRED 106.1.2 |
| |
| 10) THE ACCESSIBLE BATHROOMS NEEDS TO BE IN COMPLIANCE |
| WITH SECTION FBC 11-4.16 ? 11-4.17 ? 11-4.18 AND |
| 11-4.19. THE GRAB RAILS FOR THE BATHROOM SHOWN ON THE |
| FLOOR PLAN DO NOT MATCH THE ONE ON THE DETAIL SHEET. |
| SEE NOTES ON PLANS AND MAKE THE REQUIRED CHANGES. |
| |
| 11) SHEET D1 INDICATES THE ALTERATION TO THE EXISTING |
| EXTERIOR STAIRS AT THE SOUTH ELEVATION; HOWEVER, NO |
| CONSTRUCTION DETAIL IS PROVIDED SHOWING THE SIZE OF THE |
| TREADS AND RISERS. THE STAIRS SHALL BE IN COMPLIANCE |
| WITH FBC 1009 AND 11-4.9. |
| |
| 12) THE DRAWINGS NEED TO SHOW THE HEAD AND SILL DETAIL |
| FOR THE NEW OPENINGS. PROVIDE THE FRONT ELEVATION |
| DETAIL FOR THE NEW OPENINGS. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |
| |
| |