2008-07-08 12:01:27 | |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| PROVIDE THE FOLLOWING FOR REVIEW |
| |
| 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED |
| LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM |
| PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY |
| EASEMENTS INVOLVED. THE GENERATOR MAY NOT INTRUDE MORE |
| THAN 4 (FOUR) FEET INTO A SETBACK, AND MAY NOT EXHAUST |
| CLOSER THAN 5 (FIVE) FEET TO A DIRECT OPENING IN THE |
| RESIDENCE. CONTACT THE WPB ZONING DEPARTMENT FOR |
| DETAILS REGARDING SETBACKS. |
| |
| 2} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE |
| THE FOLLOWING: |
| |
| A) GENERATOR AND TRANSFER SWITCH MANUFACTURER |
| SPECIFICATIONS. |
| |
| |
| B) RISER DIAGRAM SHOWING LOCATIONS OF ALL |
| EQUIPMENT ELECTRICALLY. |
| |
| C) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE |
| EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE |
| STRUCTURES. |
| |
| D) MANUFACTURER SETBACK RECOMMENDATIONS FROM |
| STRUCTURES |
| |
| G) THE INSTALLATION OF THE SLAB, PAD OR BASE IS |
| INCIDENTAL TO THE ELECTRICAL CONTRACTOR?S SCOPE. WILL |
| BE REQUIRED TO BE INSPECTED. PROVIDE ENGINEERING AND |
| TIE DOWN SPECIFICATIONS FOR 140 MPH WIND LOADING. |
| |
| 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| FS, RESPECTIVELY. |
| THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| IF EXEMPTIONS APPLY. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |