Plan Review Notes For Permit 08070107 |
Permit Number |
08070107 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-11 07:57:19 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER | | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), | | FBC*106.3.3.THE JOHNS MANVILLE HAS BEEN REVIEWED, BUT | | THE TILE REVIEWED/APPROVED BY DESIGNER OF RECORD WAS | | MONIER SPANISH S. | | | | 2.)THE JOHNS MANVILLE NOA SUBMITTED IS LACKING THE | | LAST PAGE, 19, WHICH INCLUDES THE SYSTEM LIMITATIONS. | | PLEASE PROVIDE. | | | | 3.)SEE GENERAL LIMITATION 7, PAGE 19 OF THE JOHNS | | MANVILLE NOA.CALCULATIONS IN ACCORDANCE WITH RAS117 | | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF | | CONSULTANT REQUIRED FOR THE INSULATION BOARD ENHANCED | | FASTENING.PLEASE SEE THE BUILDING PLAN AND CONFIRM | | THAT DESIGN PRESSURES SPECIFIED BY DESIGNER OF RECORD | | HAVE BEEN MET OR EXCEEDED PRIOR TO RESUBMITTAL. | | | | 4.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | IN ADDITION TO THE NOA, FAC9B72.PLEASE PRINT FROM THE | | WEBSITE, WWW.FLORIDABUILDING.ORG. |
|