Plan Review Notes
Plan Review Notes For Permit 08070071
Permit Number 08070071
Review Stop E
Sequence Number 3
Notes
Date Text
2009-02-03 09:09:45 
  
  
 PROVISO
 PER 225.30, 31 AND 32 THE DISCONNECTING MEANS REQUIRED
 " SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR SIX
 CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN A
 GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A
 SWITCHBOARD. THERE SHALL BE NO MORE THAN SIX
 DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION".THE
 CIRCUITS FOR DOCK #2 MUST MEET THESE CODES. IF THE
 PANEL IS RECIRCUITED A REVISION WILL BE REQUIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  